background image

45

Содержание DB001

Страница 1: ...An ASSA ABLOY Group brand CSDB ABLOY DB001 DB002 Swing door operators Installation manual...

Страница 2: ...S SAVE THESE INSTRUCTIONS Warning Warning Do not allow children to play with fixed controls Frequently examine the installation for imbalance and signs of wear or damage to cables springs and mounting...

Страница 3: ...FS 22 TB2 and TB1 24 Connection examples Program selector PS 3A 25 Kill input 27 DA061 DA062 and DA063 microwave motion sensor 28 DA033 elbow switch and DA039 and DA049 rotary switch 29 Extension unit...

Страница 4: ...iece 3 position program switch cover DB020 swing door operators for double door EMSW swing door operator for active door swing door operator for passive door full lenght cover from hinge line to hinge...

Страница 5: ...talled in applications where it is subjected to water or snow Maximum recommended door weight width Standard arm 250 kg 1600 mm Sliding arm 100 kg 1400 mm Limit switch DB102 1A 48 VDC NO Note the maxi...

Страница 6: ...door with high speed towards open position Before fully open position the speed is reduced to low speed The door stops and the motor rotation ceases when the selected door opening angle is reached Th...

Страница 7: ...IFICATION T20 Parts 1 Base plate 2 Motor Pump 3 Magnetic valve 4 Door closer 5 Drive shaft 6 Mains connection 7 Control unit 8 Program switch 9 End plate 10 Extension unit EXB FI 11 Cover 11 7 4 6 5 3...

Страница 8: ...ion of the door hinges door clearance Check the proper function of the lock lock case striker plate Tools required Torx T8 T10 T20 and T25 Metric hexagonal key 3 4 and 6 mm Flatblade screwdriver small...

Страница 9: ...nstalling the mounting plate Operator is to be installed on the transom with the main switch located towards the hinge Use the mounting plate DB103 with the door operator ensuring the installation bas...

Страница 10: ...5 Mounting of the operator 6 pcs M6x12 Y Assembly of the operator and the standard arm DB104 to the closing side Adjustable hold open angle up to 120 50 2 17 17 37 70 37 67 100 67 87 X Y 120 20 mm DB1...

Страница 11: ...11 90 25 Nm 90 60 Assembly of the operator and the standard arm DB104 to the closing side...

Страница 12: ...r and the sliding arm DB105 to the opening side 80 Y 38 A 45 23 Min 25 Frame depth A max 125 mm 13 69 89 119 Y 139 20 mm DB106 50 mm DB107 70 mm DB108 C L 2 Mounting of the operator 6 pcs M6x12 No ext...

Страница 13: ...CLASS 2 SUPPLY MAX 24 V 5 6 7 8 9 1011 13 12 14 TB2 701500 HSO HSO LSO LSO LSC LK HSC HSC LSC 701448 LK I I I I I I I I I I I I I I I I I 25 Nm HSC or ng ALL CL 5 6 7 8 9 1011 13 12 14 TB2 Open the do...

Страница 14: ...max 45 mm 69 89 119 Y 136 20 mm DB106 50 mm DB107 70 mm DB108 80 Min 54 Y 38 A C L 2 Assembly of the operator and the sliding arm DB105 to closing side Mounting of the operator 6 pcs M6x12 No extensio...

Страница 15: ...ng the enclosed cable holders and the low voltage cables must be routed on the opposite side using the same type of cable holders ELECTRICAL CONNECTIONS Electrical connections should be made by a qual...

Страница 16: ...oove in the hydraulic unit and tightened with a lock screw By moving the limit switch sideways the opening angle is changed Note To make the adjustment easier the limit switch can be moved to the unde...

Страница 17: ...ANCE 0 0 2 2 4 4 6 6 8 8 10 10 12 12 14 14 16 16 18 18 20 20 22 22 25 25 F POCKET BALANCE 0 0 2 2 4 4 6 6 8 8 10 10 12 12 14 14 16 16 18 18 20 20 22 22 25 25 5 Closing side PUSH 35 N Opening side PULL...

Страница 18: ...not stop correctly With hold open times the distance from impulse device to door is preset 1 Adjust low opening and closing speeds 2 Adjust the operators opening torque and closing force to a low sett...

Страница 19: ...es 3 Fit the tools in the holes one from each side Note Turn both bearing sleeves simultaneously approx 165 until the setting lines in the bearing sleeves are aligned with the setting lines in the hou...

Страница 20: ...activated limit switch Contact rating 1A 48 V DC normally open Magnetic valve When door is open position the magnetic valve closes and door is kept open for adjusted hold open time Home limit switch W...

Страница 21: ...delay Hold open time Key impulse External connections Potentiometers Hold open time for outer impulse Outer HOT Hold open time can be adjusted 0 30 seconds Opening delay Opening delay can be adjusted...

Страница 22: ...ON OFF TB2 11 and 13 TB2 11 and 13 OFF AUTO TB2 11 and 13 TB2 11 and 13 AUTO OFF TB2 11 and 13 TB2 11 and 13 OFF OPEN DOOR TB2 11 and 13 TB2 11 and 13 OPEN DOOR OFF ON ON OFF ON DIP switches FS FS1 K...

Страница 23: ...e changing dip switch ON Two pieces normal DB operators Slave operator OFF Two pieces normal DB operators Master operator ON A push on the door will from closed position start an automatic opening cyc...

Страница 24: ...to TB2 7 and 8 6 When using kill input connect 24 VDC 7 0 VDC 8 Key impulse 9 0 VDC lock control 10 24 VDC for lockcase Max 375 mA 11 0 VDC 12 24 VDC for impulse devices 13 MVI impulse 14 Outer impul...

Страница 25: ...6 is needed Operation When program selector is in AUTO mode the minus goes thru diode to TB2 5 and swing door operator is ready for operation When program selector is in Manual mode the minus is disco...

Страница 26: ...AL Key impulse will open the lockcase and the door Push Go can be taken in use by setting correct Dip switch Push Go needs home limit switch DB102 The Push Go is operation when door is in closed posit...

Страница 27: ...2 9 1011121314 Kill input When kill input opens Door closes Hold open time resets Key impulse will open the lock but not the door NOTE FS1 OFF Kill Kill 0VDC Key impulse Lock control 24VDC for lock 0V...

Страница 28: ...ve motion sensor 5 4 3 2 1 Green Brown Yellow White 5 6 7 8 TB2 9 1011121314 Yellow Green White Brown Blue Pink 5 6 7 8 TB2 9 1011121314 Kill Kill 0VDC Key impulse Lock control 24VDC for lock 0VDC 24...

Страница 29: ...A049 rotary switch COM N O N C 5 6 7 8 TB2 9 1011121314 FS ON 1 2 3 4 5 6 7 8 Red Black Yellow 5 6 7 8 TB2 9 1011121314 1 2 3 NOTE FS1 OFF Add diode for example 1N4004 Diode is not included in the del...

Страница 30: ...open door from closing and will re open a closing door Presence impulse is ignored when home impulse DB102 is active The input is normally open 28 Not in use 29 Safety sensor in the opening side of th...

Страница 31: ...ION UNIT EXB FI DA001 DA002 Safety sensor in the opening side of the door 50 70 90 1 2 3 4 5 6 7 8 Jumper setting DARK ON for DA001 and DA002 26 27 28 32 31 30 29 TB4 DB102 Blanking switch will preven...

Страница 32: ...30 29 TB4 CONNECTION EXAMPLES EXTENSION UNIT EXB FI DA001 DA002 Safety sensor in the closing side of the door 0 VDC 24 VDC Presence impulse Not in use Presence detection Not in use Not in use Jumper s...

Страница 33: ...N EXAMPLES CONTROL UNIT AND EXTENSION UNIT EXB FI Electric locks EL402 EL404 EL502 CONTROL UNIT EXTENSION UNIT EXB FI 26 27 28 32 31 30 29 TB4 FS ON 1 2 3 4 5 6 7 8 NOTE FS4 ON FS5 ON 5 6 7 8 TB2 9 10...

Страница 34: ...g impulse the motor lock gets opening impulse from TB2 9 When bolt is inside lockcase operator opens the door The dip switch FS5 keeps motor lock open until door starts closing cycle If there is an ob...

Страница 35: ...1121314 FS ON 1 2 3 4 5 6 7 8 Operation When fire detector reacts the program selector goes to MANUAL mode and impulse devices won t open the door Do not connect impulse devices between TB2 5 and TB2...

Страница 36: ...tor Capacitor TB6 TB1 TB6 Passive door Active door 5 6 7 8 9 1011 13 12 14 TB1 TB6 1 4 3 2 1 4 3 2 CONNECTION OF DOUBLE DOORS Control unit for passive door Connection Motor Control 0 VDC Slave control...

Страница 37: ...control unit With this connection it is possible to feed more current to impulse devices 5 6 7 8 TB2 9 1011121314 TB1 1 3 2 Motor Control 0 VDC Slave control 24 VDC CONNECTION OF DOUBLE DOORS 5 6 7 8...

Страница 38: ...38 COORDINATOR DB109 Coordinator ensures that rebated doors are closing in right sequence Parts Hook bracket Plastic hose Return spring Wire wheel Balance spring Lever bracket...

Страница 39: ...wire through the plastic hoses and fix to the motor screws with cable straps 4 Mount the wire wheel on the passive door operator using screw and washer The wheel is to be mounted in accordance with f...

Страница 40: ...the lever bracket onto the hooks on the hook bracket including return spring 3 Install the wire through the plastic hoses and fix to the motor screws with cable straps 4 Mount the wire wheel on the pa...

Страница 41: ...121314 a x 0 a B B A A A A x B B 2 Black Red Green PC board fixing and adjustment screw Hall switch Magnet Alternative PC board fixing hole depending on mounting side and if Push or Pull Kill Kill 0VD...

Страница 42: ...is too low Lock kick valve is opened too much Pump pressure too high Low speed distance too short Motor in contact with mounting plate Magnetic valve out of operation Change setting Check motor cable...

Страница 43: ...ES AND SPARE PARTS KOODI DB110 DB102 DB103 DB104 DB105 DB106 DB107 DB108 DB114 DB115 DB113 5742075 DB116 HUOM NIMI Tool kit to change rotation direction Limit switch Mounting plate Pushing arm Sliding...

Страница 44: ...44 ACCESSORIES AND SPARE PARTS CODE DB109 5742099 5742069 5742094 NOTE NAME Coordinator Control unit CSDB EXB FI Control unit for passive door Hydraulic unit...

Страница 45: ...45...

Страница 46: ...46...

Страница 47: ...47...

Страница 48: ...r in door opening solutions dedicated to satisfying end user needs for security safety and convenience Nimike P iv ys 01 2010 DOOR CONTROL PRODUCT MANAGEMENT 25 01 2010 FH11 XXXXXX Some of the materia...

Отзывы: