ABLE BEKA associates BA648CF-P Скачать руководство пользователя страница 8

6

Please  refer  to  the  quick  set-up  procedure  in  the
BEKA PROFIBUS PA Display – Fieldbus Interface
Guide
.

5.2.4  Reset the instrument to node factory
          defaults           ‘rESEt’
The  BA648CF-P  may  be  reset  to  the  factory
defaults that are shown below:

Security Code

0000 (disabled)

Device address

126

For each of the eight inputs:

Decimal point

XXX.XX

Bar Type

Left

Bar lower limit

0.0

Bar Upper limit

100.0

Gain

1.0

Offset

0.0

To  reset  the  BA648CF-P  select  ‘rESEt’  in  the
configuration  menu  by  operating  the 

  or 

button.  To  enter  the  function  press  P  which  will
reveal  ‘0000’  with  the  left  hand  digit  flashing.  To
prevent accidental use of this function, ‘5urE’ must
be  entered  to  confirm  that  the  instrument  is  to  be
reset.

Using the 

 or 

 button set the flashing digit to ‘5’

and press the P button to move control to the next
digit  which  should  be  set  to  ‘u’.    When  the  four
letters of ‘5urE’ have been entered operating the E
button  will  reset  the  BA648CF-P  to  the  factory
defaults.  Any existing configuration and addresses
will be lost when the instrument is reset.

FIG 4 Node configuration menu

5.3  Listener configuration menu
When  used  as  a  fieldbus  listener  the  BA648CF-P
is  not  visible  to  the  fieldbus  host  and  can  only  be
configured  using  the  front  panel  push  buttons
shown in Fig 2.

The  listener  configuration  menu  is  separated  into
three  sections,  ‘SCAn’,  ‘LISt’  and  ‘Edit’,  plus  three
housekeeping functions ‘CodE’, ‘tYPE’ and  ‘rESEt’
as shown in Fig 6.

‘SCAn’  is  the  simplest  method  of  configuration  if
the addresses of the data sources to  be  displayed
by the BA648CF-P listener are not known.

In  the  ‘SCAn’  function  pressing  the  P  button
causes  the  BA648CF-P  listener  to  search  the
fieldbus  segment  to  which  it  is  connected  for  all
data  sources.        The  hexadecimal  device
addresses  for  each  data  source  are  displayed  as
shown in Fig 5.

The 

  and 

  push  buttons  scroll  the  display

through  all  the  data  sources  on  the  segment
showing  the  source  and  destination  address  for
each  one.      To  aid  identification,  operating  the  P
button  will  preview  the  value  of  the  data  at  the
selected  addresses  with  a  zero  index  i.e.  the  first
five  bytes  in  the  data  string.      If  the  format  of  the
data  is  not  DS-33  (status  +  float)  ‘no  dAt’  will  be
displayed.    The  selected  source  and  destination
addresses  may  be  allocated  to  one  of  the  eight
BA648CF-P listener inputs in-1, to in-8.  Operating
the  P  button  will  reveal  the  current  listener  input
which  may  be  changed  using  the 

  or 

  push

button, when set as required, operating the E push
button  will  enter  the  allocation.    If  the  process
variable to be displayed is located further along the
data  stream  i.e.  has  an  index  greater  than  5,  the
required  index  must  be  entered  via  the  index  ‘ind’
function in the edit sub-menu.

A  worked  configuration  example  illustrating  this
procedure is contained in the Quick Set-up section
of  the  BEKA  PROFIBUS  PA  Display  –  Fieldbus
Interface Guide.

Fig 5  Device Addresses

If the source and destination  addresses  and  index
of  the  process  variable  to  be  displayed  by  the
BA648CF-P  listener  are  known,  they  may  be
directly  entered  via  the  edit  sub-menu.    This  sub-
menu also provides full control of both the numeric
and bargraph display parameters.

Содержание BEKA associates BA648CF-P

Страница 1: ...Supplied by Call us on 44 0 118 916 9420 Email info 247able com com Installation Maintenance Instructions BA648CF P ...

Страница 2: ...hill Lower Earley Reading Berkshire RG6 4UT UK Tel 44 0 118 9311188 Email info able co uk Aberdeen Office Unit 6 Airside Business Park Kirkhill Industrial Estate Dyce Aberdeen AB21 0GT UK Tel 44 0 1224 725999 Email ab able co uk Internet www able co uk e procurement www 247able com Registered in England No 01851002 VAT No GB 417 2481 61 ...

Страница 3: ...Issue 2 23 rd June 2011 BA648CF P PROFIBUS PA Panel mounting 8 variable Fieldbus Indicator Issue 2 ...

Страница 4: ...t parameters 5 4 3 Enter address display parameters 5 4 4 Enable selected input 5 4 5 Enter source address 5 4 6 Enter destination address 5 4 7 Enter Index 5 4 8 Decimal point position 5 4 9 Configuration of bargraph 5 4 10 Scale numeric display 5 4 11 Access code for listener configuration menu 5 4 12 Change from fieldbus listener to fieldbus node 5 4 13 Reset the listener to factory defaults 6 ...

Страница 5: ...on label There is an alternative version of the fieldbus display order code BA648CF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes installation configuration and use of the BA648CF P as a PROFIBUS PA listener and as a PROFIBUS PA node For additional node configuration information please refer to the BEKA PROFIBUS PA Display Fieldbus Interface Guide wh...

Страница 6: ...r panel mounting clips Fig 2 BA648CF P dimensions 4 2 Installation Procedure a Insert the BA648CF P into the instrument panel cut out from the front of the panel b Fix panel mounting clips to opposite sides of the instrument and tighten until the instrument is secure Four clips are required to achieve an IP66 seal between the instrument enclosure and the panel c Connect the panel wiring to the rea...

Страница 7: ...nd digit flashing which may be changed by operating the or button When set as required operating the P button will transfer control to the next digit that may be adjusted in the same way When all digits are set as required operating the E button will enter the new address and the indicator will restart in the display mode after completing the initialisation sequence If the address is not changed o...

Страница 8: ...ddresses of the data sources to be displayed by the BA648CF P listener are not known In the SCAn function pressing the P button causes the BA648CF P listener to search the fieldbus segment to which it is connected for all data sources The hexadecimal device addresses for each data source are displayed as shown in Fig 5 The and push buttons scroll the display through all the data sources on the seg...

Страница 9: ...7 ...

Страница 10: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 5 4 3 Enb Enable selected input Enables each of the eight listener inputs in 1 to in 8 to be enabled or disabled without affecting any parameters See section 5 4 4 SrC Enter Source Address Allows hexadecimal fieldbus device source...

Страница 11: ...source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a listener input any previous allocation will be overwritten If the required process variable has an index above 5 i e it is not the first five bytes in the data string the required index should be ente...

Страница 12: ...y mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 5 4 9 Configuration of bargraph display bAr This function contains three sub functions that enable the bargraph justify its position and define the relationship between the bargraph and the instrument s numeric display Sub function b ...

Страница 13: ...revised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 5 4 12 Change from fieldbus listener to fieldbus node tYPE This function enables the BA648CF P to be conditioned as a fieldbus node or as a fieldbus listener To change the function of the instrument select tYPE in the listener configuration menu using...

Страница 14: ...ration after a few seconds the firmware version will be displayed prior to entering the operational mode 6 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE If a BA648CF P fails after it has been functioning correctly the table shown in section 6 1 may help to identify the cause of the failure If this procedure does not reveal the cause of the fault it is recommen...

Страница 15: ...d a scale for the horizontal bargraph 7 2 Tag number The BA648CF P can be supplied with a thermally printed tag number on the rear panel adjacent to the terminals 7 3 BEKA PROFIBUS PA Display Fieldbus Interface Guide The BEKA PROFIBUS PA Display Fieldbus Interface Guide contains commissioning information for the BA648CF A copy may be requested from the BEKA sales office or downloaded from the BEKA...

Отзывы: