Page 21
INSTALLATION INSTRUCTION
1.
Proper clearances must be maintained for adequate air circulation. Adequate ventilation must be provided while
operating this stove.
2.
The stove must be placed on solid masonry, solid concrete, or when installing on combustible floor, on a UL
1618 listed floor protector or flammable floor must be protected by in-sulating plate ( steel, brass, marble, stone,
ceramic tiles, etc.) . The base must extend at least 18" (46 cm) beyond the front of the stove and 8"(20 cm) to the
sides, and MUST extend under the stove pipe. (Check local building codes and fire protection ordinances.) Floor
protector minimum size; „Concept 2 Air“ 56“ x 47“; „Concep 2 mini Air“ 39“ x 47“
3.
The stove must have its own flue. DO NOT CONNECT THIS UNIT TO A CHIMNEY SERVING OTHER
APPLIANCES.
4.
Connect flue collar to the stove and adapter for creosote leakage. The crimped end of the stove pipe must be in-
stalled facing down to fit inside the adapter. Figure 1, page 11
5.
Use three (3) sheet metal screws at each joint of stove pipe and adapter to firmly hold stove pipe together. Use 6"
round black/blue stove pipe (Listed to UL 103, Type HT and evaluat-ed to CAN/ULC-S629-M87) NOT
galvanized pipe. DO NOT CONNECT THIS STOVE TO ANY AIR DISTRIBUTUIN OR DUCT SYSTEM.
6.
Slope any horizontal stove pipe upward toward the chimney at least 1/4 inch for each foot of horizontal run.
7.
You must have at least 18" of clearance between any horizontal
single wall pipe and ceiling.
8.
The stove pipe must NOT extend to far into the chimney flue.
9.
It is recommended that no more than two (2) 90 degree bends be used in the stove pipe installation.
10.
Connect to 6" inspected masonry chimney or 6" UL Type HT listed chimney.
MASONRY CHIMNEY
Before using an existing masonry chimney, clean the chimney, inspect the flue liner and make any repair
needed to be sure it is safe to use.
If connector stove pipe must go through a combustible wall before entering the masonry chim-ney, consult a
qualified mason or chimney dealer. The installation must conform to local fire codes, and NFPA 211.
Do NOT connect this stove into the same chimney flue as the fireplace or flue from another stove. If there is a
cleanout opening in the base of the chimney, close it tightly.
UL LISTED CHIMNEY
Carefully follow chimney manufacturer's instructions. Us only a UL 103 Type HT Listed Resi-dential Type and
Building Heating Appliance Chimney. The top of the chimney must be at least three (3) feet above the roof and
be at least two (2) feet higher than any point of the roof within ten (10) feet.
NOTE: FLOOR EMBER PROTECTION IS REQUIRED FOR SPARK AND ASH SHIELDING, NOT
FOR LIMITING FLOOR TEMPERATURE FROM THE RADIANT HEAT OF THE APPLIANCE.
A PROFESSIONAL, LICENSED HEATHING AND COOLING CONTRACTOR SHOULD BE
CONSULTED IF YOU HAVE QUESTIONS REGARDING THE INSTALLATION OF THIS SOLID
FUEL BURNING APPLIANCE.
Содержание Concept 2 air
Страница 1: ...Founded in 1990 TECHNICAL MANUAL for solid fuel burning cookers Concept 2 air and Concept 2 mini air ...
Страница 27: ...Page 24 ...
Страница 33: ...Page 30 The position and size of connections Concept 2 Air Fig 1 Concept 2 Mini Air Fig 2 ...
Страница 37: ...Page 34 CONCEPT 2 MINI AIR ...
Страница 38: ...Page 35 Parts Concept 2 Mini Air ...
Страница 39: ...Page 36 Parts Concept 2 Air ...