16
ABB Zenith
■
MX
1
50/MX250
S
eries
Modbus
Net
w
ork
Card
(71R-22
0
0)
A
B
SEE NOTE 6
PS-5140
NETWORK PLUG
CONNECTOR
VERIFY POLARITY
CONNECTIONS
50W-1208
RS232/485
CONVERTER
50P-2035
MODBUS
NETWORK CARD
ASSEMBLY
ADDRESS/STATUS INDICATOR LEDs
(REF. PG.1, FIG. 2)
CONFIGURATION JUMPER (J4)
(NOTE 2)
SEE NOTE 1
Appendix
D
Connections
for
Con
figuring
and
T
esting
the
Modbus
Card
MODBUS NETWORK CARD DEFAULT SETTINGS
SLAVE ADDRESS 1
RTU MODE
8 DATA BITS, 9600 BAUD, NO PARITY, 2 STOP BITS.
NOTES:
1.
USE TWISTED PAIR CABLE (BELDEN 8471, 16 AWG) (ABB ZENITH
PART # WMW-453).
2.
CONFIGURATION JUMPER (J4) MUST BE INSTALLED TO CHANGE MODBUS
ADDRESS AND MODE. REMOVE FOR NORMAL OPERATION.
3.
MODBUS NETWORK CARD ASSEMBLY MUST BE INSTALLED ON THE CON-
TROLLER. REFER TO APPENDIX F.
4.
USE SOFTWARE PROGRAMMING PACKAGE 50P-1111. REFER TO PAGE #
“CONFIGURING A MODBUS NETWORK CARD.”
5.
TO TEST THE MODBUS NETWORK, REFER TO PAGE # “TESTING A MODBUS
NETWORK” PROCEDURE.
6.
CONNECT TO THE SERIAL PORT OF THE PC WHICH HAS THE 50P-1111
SOFTWARE PACKAGE.