ABB | SACE Tmax XT
54 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Protections | 8 - Voltage protections
OV Protection
U9
t
t9
V
OV
Function
The protection sends a TRIP command if one or more line-to-line voltages detected by the unit exceed
threshold U9 for longer than t9.
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 88)
• the graph with trip curve (page 100)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
OFF
Threshold U9
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un) and
can be set within the range: 1 Un to 1.5 Un in 0.001 Un steps
1,05 Un
Time t9
This is the trip time of the protection; the value is given in seconds and can
be set within a range: 0.05 s to 120 s, in 0.01 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 75).
UV2 Protection
U15
t
t15
v
UV2
Function
UV2 protection functions in the same way as UV protection: the protection sends a TRIP command if one or
more line-to-line voltages detected by the unit drop below threshold U15 for longer than t15.
It is independent of UV protection, thus thresholds and functions of the two protections can be programmed
so as to take advantage of different plant solutions (example: signaling with UV and open command with UV2
or vice versa, or both for signaling or tripping).
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 88)
• the graph with trip curve (page 99)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
OFF
Threshold
U15
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un) and
can be set within the range: 0.05 Un to 1 Un in 0.001 Un steps
0,9 Un
Time t15
This is the trip time of the protection; the value is given in seconds and can
be set within a range: 0.05 s to 120 s, in 0.01 s steps
5 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 75).
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...