ABB | SACE Tmax XT
52 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Protections | 7 - Standard Protections
Harmonic Distortion Protection
Allows an alarm to be activated in the case of distorted wavefoms.
The protection can be enabled in the
Measurements
menu; if enabled an alarm is activated (page 36).
IMPORTANT: the protection does not handle the trip, just the signal
T Protection
T protection protects against abnormal temperatures measured and transmitted to the sensor inside the unit;
temperature verification is always active and includes three operating states:
State
Temperature range [°C]
Ekip Touch actions
Standard
-25 < t < 70
Normal operation; display on
(1)
Warnings
-40 < t < -25 or 70 < t < 85
Warning led @ 0.5 Hz; display on
(1)
Alarm
t < -40 or t > 85
Display off; Alarm and Warning leds @ 2 Hz; TRIP if Trip
enable is activated
(1)
the display remains on within range: -20°C / +70°C
All protections enabled in the unit are active in all operating states.
The Trip Enabling parameter can be enabled in the
Settings
-
Circuit breaker
menu in order to handle an open
command if an alarm occurs (page 37).
Hardware Trip Protection
Hardware Trip protects against connection errors in Ekip Touch and is available in the
Settings
-
Circuit
breaker
-
Hardware Trip
menu (page 36).
If enabled, with the CB closed, if one or more of these events are detected:
• current sensors disconnected (phase or external if enabled)
•
Rating Plug
disconnected.
•
Trip Coil
disconnected
• faults inside the unit
the alarm is signaled and a TRIP command is transmitted.
IMPORTANT:
• the protection trips if the error statuses persist for more than one second
• the signal is activated in the case of an alarm due to Trip coil disconnection and, in the presence
of Vaux, output YO is commanded until the Trip unit detects the CB Open state (make sure that
YO, Ekip Actuator, YO coil supply are present)
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...