4 - Operating features
Introduction
Ekip Touch has been developed and certified to function in specific environmental, electrical and mechanical
conditions; full details are available in the
Technical catalog
(page 4).
The following sections describe the electrical and power supply characteristics that enable Trip unit and the
relative electronic accessories to operate correctly.
Electrical characteristics
The Ekip Touch measurement and protection functions described in this document are provided with primary
voltage and current values within the following nominal ranges:
Parameter
Operating limits
Primary current (line-to-line)
0,004 ÷ 16 In
(1)
Primary voltage (line-to-line)
5 ÷ 690 V AC
(2)
Rated frequency
45 ... 55 Hz (with fn= 50 Hz) / 54 ... 66 Hz (with fn= 60 Hz)
Peak factor
Complying with standard IEC 60947-2
(1)
based on each phase; In refers to the nominal size defined by the Rating plug installed on the Trip unit,
available in models from 800 A to 1600 A
(2)
rated highest line-to-line voltage connected directly to Trip unit, also using sockets inside the CB; external
transformers must be used for higher voltage values, consult the chapter dedicated to the Measurement
module on page 137
Ekip Touch can self-supply itself directly from the internal current sensors:
Parameter
Operating limits
Minimum three-phase turn-on current
82 A
Auxiliary power supply
Ekip Touch can be connected to an external auxiliary supply source, which is useful when certain functions
such as communication via Local Bus, recording manual operations, certain measurements and the
datalogger must if available.
The auxiliary supply can be provided by modules from the
Ekip Supply
range (further details about operation
are given on page 140) or by direct connection to the terminal box.
Direct connection must guarantee the following operating conditions:
Parameter
Operating limits
Voltage
24 V DC galvanically isolated
Tolerance
±10%
Maximum ripple
±5%
Maximum inrush current @ 24 V
10 A per 5 ms
Maximum rated power @ 24 V
4 W
Connection cable
Insulated with grounding cable (same characteristics
as Belden 3105A/B or higher)
IMPORTANT: if connection is direct, the power supply must be galvanically insulated
and provide the insulation characteristics established by standard IEC 60950 (UL
1950) or equivalent.
Содержание XT7
Страница 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...
Страница 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...
Страница 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...
Страница 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...
Страница 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...
Страница 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...
Страница 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...
Страница 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...
Страница 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...
Страница 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...
Страница 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...
Страница 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...
Страница 193: ...1SDH001821A1002 ECN000135670...