VMAX
- INSTALLATION AND SERVICE INSTRUCTIONS
D
H
W
I I
Circuit breaker
Vmax 12
Vmax 17
Vmax/F 12 (*)
Vmax/F 17 (*)
Vmax 15
Fixed version
•
•
-
-
•
Fixed version for ABB UniGear 500R panel
-
-
•
•
-
Standards
IEC 62271-100
•
•
•
•
-
CEI EN62271-100 (file 7642)
•
•
•
•
-
C37.54, C37.09, C37.04, C37.55
-
-
-
-
•
UL Recognized Component Mark
-
-
-
-
•
Rated voltage
Ur [kV]
12
17.5
12
17.5
15
Rated insulation voltage
Us [kV]
12
17.5
12
17.5
15
Withstand voltage at 50 Hz
Ud (1 min) [kV]
28
38
28
38
36 (at 60 Hz)
Impulse withstand voltage
Up [kV]
75
95
75
95
95
Rated frequency
fr [Hz]
50–60
50–60
50–60
50–60
60
Rated normal current (40 °C)
Ir [A]
630
1250
630
1250
630
1250
2000
630
1250
2000 (
**)
1200
Rated breaking capacity
(rated symmetrical
short-circuit current)
Isc [kA]
16
16
16
16
-
-
-
-
-
-
-
20
20
20
20
-
-
-
-
-
-
-
25
25
25
25
25
25
25
25
25
25
25 (3 cycles)
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5 (3 cycles)
Rated-short time
withstand current (3s)
Ik [kA]
16
16
16
16
-
-
-
-
-
-
-
20
20
20
20
-
-
-
-
-
-
-
25
25
25
25
25
25
25
25
25
25
25 (2s)
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5 (2s)
Making capacity
Ip [kA]
40
40
40
40
-
-
-
-
-
-
-
50
50
50
50
-
-
-
-
-
-
-
63
63
63
63
63
63
63
63
63
63
65
80
80
80
80
80
80
80
80
80
80
82
Operation sequence
[O – 0.3 s – CO – 15 s – CO]
•
•
•
•
-
[O – 0.3 s – CO – 3 min – CO]
-
-
-
-
•
Opening time
[ms]
33–60
33–60
33–60
33–60
27 ... 32.5
Arc duration
[ms]
10–15
10–15
10–15
10–15
10–17.5
Total breaking time
[ms]
43–75
43–75
43–75
43–75
<50
Closing time
[ms]
30–60
30–60
30–60
30–60
45–80
Maximum
overall
dimensions
H [mm/in]
496
534
543
543
543
543
534/21.02
W [mm/in]
416
416
416
416
416
416
416/16.38
D [mm/in]
421
456
461
562
461
562
456/17.95
Pole center I [mm/in]
133–155
133–155
133
133
133
133
133/5.24
Weight
[kg/lb]
77
77
77
80
77
80
77/169.40
Standardized table of dimensions
1VCD
003279
003279
003516
003558
003516
003558
003279
Operating temperature
[°C]
-5 ... +40
-5 ... +40
-5 ... +40
-5 ... +40
-30 ... +40
Tropicalization
IEC: 60068-2-30, 60721-2-1
•
•
•
•
-
Electromagnetic compatibility
IEC 62271-1
•
•
•
•
-
(*) This version cannot be sold loose; this version can only be supplied for
2000 A; Vmax/FH version must be ordered together with ABB UniGear
500R switchgear.
(**) Up to 15 kV
5.3.2. Standard fittings for fixed circuit breakers
The basic versions of the fixed circuit breakers
are three-pole and fitted with:
• EL type manual operating mechanism
• mechanical signalling device for closing springs
charged/discharged
• mechanical signalling device for circuit breaker
open/closed
• closing pushbutton
• opening pushbutton
• operation counter
• set of ten circuit breaker open/closed auxiliary
contacts
Note: application of the shunt opening release and/or additional shunt
opening release foresees the use of one or two auxiliary make contacts
(normally open), thereby reducing the number of auxiliary contacts available.
• lever for manual closing spring charging
• auxiliary circuit support terminal box.
—
5. Description
5.3.1. General characteristics of fixed circuit breakers