11.  Spare parts and accessories

  All assembly operations of spare parts/

accessories must be carried out in 
accordance with the instructions enclosed 
with the spare parts themselves, by ABB 
personnel or by suitably qualified customer 
personnel with in-depth knowledge of the 
apparatus (IEC 60694) and of all the 
Standards aimed at ensuring that these 
interventions are carried out in safe 
conditions. If maintenance is carried out by 
the customer’s personnel, responsibility for 
the interventions remains with the 
customer. Before proceeding with any 
operation, always make sure that the circuit 
breaker is open, the springs discharged and 
that it is not energised (medium voltage 
circuit and auxiliary circuits).

When ordering circuit breaker spare parts/
accessories, refer to the ordering sales codes 
indicated in the technical catalogue and always 
state the following:

• 

type of circuit breaker

• 

rated voltage of the circuit breaker

• 

rated nominal current of the circuit breaker

• 

breaking capacity of the circuit breaker

• 

serial number of the circuit breaker

• 

rated voltage of any electrical spare parts.

Please contact our Service office to check on 
availability and to order spare parts.

11.1   List of spare parts

• 

Opening release

• 

Supplementary opening release

• 

Undervoltage release

• 

Contact for signalling undervoltage release 
energised/deenergised

• 

Time delay device for undervoltage release

• 

Mechanical override for undervoltage release

• 

Closing release

• 

Spring loading geared motor with electrical 
signalling of springs loaded

• 

Gearmotor thermomagnetic protection circuit 
breaker

• 

Contact for signalling gearmotor protection 
circuit breaker open/closed

• 

Contact for signalling closing springs loaded/
discharged

• 

Auxiliary contacts of the circuit breaker

• 

Opening solenoid

• 

Open position key lock

• 

Opening pushbutton protection

• 

Closing pushbutton protection

• 

Set of six main isolating contacts

• 

K7 sensors for REF601

• 

REF601 protection releases

• 

Connector complete with sheath

• 

Wheel Kit

• 

Operation counter

• 

Complete pole.

Содержание VD4 Series

Страница 1: ...on program 3 1 Packing and transport 4 2 Inspection on arrival 5 3 Storing 6 4 Handling 7 5 Description 8 6 Instructions for circuit breaker operation 21 7 Installation 23 8 Putting into service 26 9...

Страница 2: ...standards and laws so as to ensure that the installations are constructed in accordance with the rules of good workmanship and safety in the work place Strictly comply with the instructions in this ma...

Страница 3: ...ent guidelines The manufacturing processes are implemented in accordance with the environmental protection I Foreword II Environmental protection program Besides this manual it is therefore always nec...

Страница 4: ...d transport The circuit breaker is shipped in special packing in the open position and with the springs discharged Each piece of apparatus is protected by a plastic cover to prevent water from infiltr...

Страница 5: ...n sent by ABB Before proceeding with any operation always make sure that the springs of the operating mechanism are discharged and that the apparatus is in the open position The following documents ac...

Страница 6: ...paratus cannot be installed immediately it must be repacked in the original packing materials Insert at least one standard packet of special hygroscopic substance per piece of apparatus inside the pac...

Страница 7: ...is in the open position When handling the apparatus take great care to prevent the insulating parts and the terminals of the circuit breaker from being stressed The apparatus must not be handled by in...

Страница 8: ...ed in all VD4 series circuit breakers with frontal control The circuit breaker can be remote controlled when fitted with dedicated electrical accessories gearmotor opening and closing release The oper...

Страница 9: ...c switchgear 230 mm pole center distance Depending on the version they can be equipped on request with two or three current sensors and with a REF 601 series device for protection against overcurrents...

Страница 10: ...l dimensions maximum H mm 785 785 785 W mm 317 317 317 D mm 1029 1 1170 2 1029 1 1170 2 1029 1 1170 2 Pole center distance P mm 230 300 230 300 230 300 Weight 3 kg 65 1 67 2 65 1 67 2 65 1 67 2 Applic...

Страница 11: ...imum H mm 785 785 785 W mm 317 317 317 D mm 1029 1 1170 2 1029 1 1170 2 1029 1 1170 2 Pole center distance P mm 230 300 230 300 230 300 Weight 3 kg 65 1 67 2 65 1 67 2 65 1 67 2 Application of REF 601...

Страница 12: ...Closing time ms 30 60 30 60 30 60 Overall dimensions maximum H mm 740 740 740 W mm 315 315 315 D mm 1005 1005 1005 Pole center distance P mm 230 230 230 Weight 3 kg 65 65 65 Application of REF 601 pr...

Страница 13: ...100 Rated voltage Ur kV 12 17 5 24 Rated insulation voltage Us kV 12 17 5 24 Withstand voltage at 50 Hz Ud 1 min kV 281 1 38 1 50 Impulse withstand voltage Up kV 75 95 125 Rated frequency fr Hz 50 60...

Страница 14: ...springs in the manual mode built into the operating mechanism 6 indicator for closing springs loaded relieved The basic wiring ends in the terminal box This latter is equipped with a withdrawable part...

Страница 15: ...re The terminal box is actually situated at the front and projects over the upper edge of the enclosure the front enclosure has a transparent sliding shutter over the mechanical indicators the operati...

Страница 16: ...6 16 20 VD4 R 12 06 20 25 VD4 R 12 06 25 800 16 VD4 R 12 08 16 20 VD4 R 12 08 20 25 VD4 R 12 08 25 1250 16 VD4 R 12 12 16 20 VD4 R 12 12 20 25 VD4 R 12 12 25 17 5 630 12 5 VD4 R 17 06 12 16 VD4 R 17 0...

Страница 17: ...12 06 20 25 VD4 L 12 06 25 800 16 VD4 L 12 08 16 20 VD4 L 12 08 20 25 VD4 L 12 08 25 1250 16 VD4 L 12 12 16 20 VD4 L 12 12 20 25 VD4 L 12 12 25 17 5 630 12 5 VD4 L 17 06 12 16 VD4 L 17 06 16 20 VD4 L...

Страница 18: ...12 16 VD4 R SEC 12 08 16 20 VD4 R SEC 12 08 20 25 VD4 R SEC 12 08 25 1250 12 5 VD4 R SEC 12 12 12 16 VD4 R SEC 12 12 16 20 VD4 R SEC 12 12 20 25 VD4 R SEC 12 12 25 17 5 630 12 5 VD4 R SEC 17 06 12 16...

Страница 19: ...12 06 25 800 12 5 VD4 L SEC 12 08 12 16 VD4 L SEC 12 08 16 20 VD4 L SEC 12 08 20 25 VD4 L SEC 12 08 25 1250 12 5 VD4 L SEC 12 12 12 16 VD4 L SEC 12 12 16 20 VD4 L SEC 12 12 20 25 VD4 L SEC 12 12 25 1...

Страница 20: ...it breaker opening 35 70 Un circuit breaker closing 85 110 Un Power on inrush Ps 150 W Inrush time 150 ms Holding power Pc 3 W Opening time 60 80 ms Insulation voltage 2000 V 50 Hz for 1 min Specifica...

Страница 21: ...Undervoltage release disabled The circuit breaker can also be closed if the undervoltage release is not supplied with power 6 2 Operating and signalling parts VD4 circuit breakers guarantee a minimum...

Страница 22: ...ading operation the gearmotor stops and automatically continues with the spring loading operation once the power returns However it is always possible to complete the loading operation in the manual m...

Страница 23: ...tions required for installation putting into service service and maintenance must be carried out by qualified personnel The areas through which power conductors or auxiliary circuit conductors are rou...

Страница 24: ...cuitbreaker terminals or the monoblocs of the cubicles sized according to the electrodynamic stress caused by the short circuit current of the installation The circuit breaker terminals are always sil...

Страница 25: ...lt taking care to prevent the insulating parts from being stressed Use of DIN class 8 8 standard bolts is recommended also with reference to the indications in table 2 Make sure that the connections d...

Страница 26: ...tion resistance should be several M and must remain constant over time 2 Auxiliary circuits Make sure that the connections to the control circuit are correct proceed with the relative power supply Nor...

Страница 27: ...tions during the maintenance operations Before proceeding with any operation make sure that the circuit breaker is open with the springs discharged and that it is not powered medium voltage circuit an...

Страница 28: ...richloroethane trichloroethylene or carbon tetrachloride 9 3 2 Actuator and transmission system Circuit breakers up to 25 kA The actuator trip box the shock absorber and all the other components of th...

Страница 29: ...dication due to the capacitive effect In this case the cables must not be removed If maintenance is carried out by the customer s personnel responsibility for the interventions remains with the custom...

Страница 30: ...means that use of vacuum interrupters is absolutely safe at the rated service voltage application of the withstand voltage at power frequency according to the IEC 62271 100 and VDE 0670 Standards is s...

Страница 31: ...r rated voltage of the circuit breaker rated nominal current of the circuit breaker breaking capacity of the circuit breaker serial number of the circuit breaker rated voltage of any electrical spare...

Страница 32: ...310 0 0 6 0 2 5 4 6 5 6 7 1 239 6 7 5 2 1 282 27 7 141 21 5 4 1 18 132 5 97 95 75 5 100 22 5 14 187 1 1 1 1 8 45 VD4 R VD4 L VD4 R SEC VD4 L SEC INSTALLATION AND OPERATING INSTRUCTIONS 32 12 Overall d...

Страница 33: ...0 160 2 5 2 8 3 139 310 0 0 1 5 4 6 0 0 6 0 2 282 270 20 5 6 7 1 2 1 239 6 7 5 21 5 7 141 18 4 1 95 132 5 22 5 100 75 5 187 1 1 1 1 2xM10 45 2 8 3 MEDIUM VOLTAGE PRODUCTS 33 Fixed circuit breaker with...

Страница 34: ...2 310 5 4 6 5 6 7 1 6 7 5 2 1 239 21 5 27 7 282 141 4 1 18 132 5 97 95 75 5 100 22 5 187 14 2 8 3 1 1 2xM10 1 1 45 VD4 R VD4 L VD4 R SEC VD4 L SEC INSTALLATION AND OPERATING INSTRUCTIONS 34 12 Overall...

Страница 35: ...5 7 3 2 4 10 2 8 3 310 0 0 1 5 4 6 0 0 6 0 2 282 270 20 21 5 239 5 6 7 1 2 1 6 7 5 7 141 18 4 1 92 132 5 95 22 5 100 75 5 1 1 1 1 M10 45 2 8 3 MEDIUM VOLTAGE PRODUCTS 35 Fixed circuit breaker with lh...

Страница 36: ...22 40 282 315 141 46 239 21 5 30 5 650 576 20 70 5 740 116 5 53 42 42 4 x M8 21 deep 55 95 no C S 382 14 R7 4 98 24 5 30 25 40 202 5 VD4 R VD4 L VD4 R SEC VD4 L SEC INSTALLATION AND OPERATING INSTRUCT...

Страница 37: ...2xM10 22 deep 237 5 72 426 6 2 5 269 40 750 40 422 79 5 21 222 152 28 141 187 yes C S 78 5 107 5 382 R7 4 24 5 98 30 25 40 12 5 95 no C S 42 42 4 x M8 21 deep 55 MEDIUM VOLTAGE PRODUCTS 37 Fixed circ...

Страница 38: ...26 5 17 5 17 5 53 5 83 14 156 16 213 30 198 141 21 5 39 5 72 5 119 5 121 5 1 5 3 5 3 5 5 6 3 2 VD4 R VD4 L VD4 R SEC VD4 L SEC INSTALLATION AND OPERATING INSTRUCTIONS 38 12 Overall dimensions Detail...

Страница 39: ...he matters established by the ISO 14001 Standards ABB provides its skills and assistance to facilitate the recycling and disposal process for products at the end of their life It is always necessary t...

Страница 40: ...more information please contact Your sales contact abb com mediumvoltage Your contact center abb com contactcenters More service information abb com service The data and illustrations are not binding...

Отзывы: