5.4.1. General characteristics of fixed circuit-breakers
General characteristics of fixed circuit-breakers (36 kV)
Circuit-breaker
VD4 36
Standards
IEC 62271-100 •
VDE 0671; CEI 17-1 (File 1375) •
Rated voltage
Ur [kV] 36
Rated insulation voltage
Us [kV] 36
Withstand voltage at 50 Hz
Ud (1 min) [kV] 70
Impulse withstand voltage
Up [kV] 170
Rated frequency
fr [Hz] 50-60
Rated normal current (40 °C)
Ir [A]
Rated breaking capacity
(rated short-circuit breaking current symmetrical)
Isc [kA]
Rated short-time withstand current (3s)
Ik [kA]
Making capacity
Ip [kA]
Operation sequence
[ O - 0.3 s - CO - 3 min - CO ]
Opening time
[ms] 35 ... 60
Arcing time
[ms] 10 ... 15
Total breaking time
[ms] 45 ... 75
Closing time
[ms] 60 ... 80
Maximum
overall
dimensions
H [mm]
W [mm]
D [mm]
Pole distance P [mm]
Weight
[kg]
Operating temperature
[°C] - 5 ... + 40
Tropicalization
IEC: 60068-2-30, 60721-2-1 •
Electromagnetic compatibility
IEC: 62271-1 •
D
H
W
P P
1250
--
31.5
--
--
31.5
--
--
80
--
•
564
778
468
275
150
1600
--
31.5
--
--
31.5
--
--
80
--
•
2000
--
31.5
--
--
31.5
--
--
80
--
•
564
778
468
275
150
564
778
468
275
170
2500*
--
31.5
--
--
31.5
--
--
80
--
•
Note: * - To be released. Contact ABB