ABB UNO-DM-3.3-TL-PLUS-US Скачать руководство пользователя страница 2

13.

Grid support functions

11.

AFD (arc fault detection)

10.

Commissioning

9.

User Interface

12.

Response to abnormal conditions

UNO-DM-3.3_3.8_4.6_5.0-TL-PLUS-US-Quick Installation Guide EN-RevD

EFFECTIVE 2017-09-06

© Copyright 2017 ABB. All Rights Reserved.

Specifications subject to change without notice. 

8.

AC Output connection

Technical Data

14.

Contact us

www.abb.com/solarinverters

The inverter is equipped with advanced grid support functionality that is useful to support reactive loads and also assist in reliable operation of the utility grid in 

the presence of a large number of distributed energy generation sources. This section provides an overview of the available grid support functions.

The parameters related to the grid support functions that are in this inverter can be modified by:

- Accessing the embedded Web User Interface.

- Accessing to settings under the Service menu requires a time-limited password, which can be obtained by calling ABB solar inverter technical support at 1-877-261-1374. 

1.  Voltage ride-through 

This inverter provides parameters to respond to undervoltage and overvoltage events. The inverter is designed to operate normally within the specified 

operating range. If voltage excursions occur, the inverter is designed to continue operating normally or cease to export power for a specified delay. After this 

programmed delay, the inverter disconnects from the grid if the voltage is still out of its normal range. The voltage ride-through parameters can be adjusted.

2.  Frequency ride-through 

This inverter provides parameters to respond to underfrequency and overfrequency events. If frequency excursions occur, the inverter is designed to continue 

operating normally for a specified delay. Beyond this programmed delay, the inverter disconnects from the grid in the event of an abnormal voltage condition. 

The frequency ride-through parameters can be adjusted.

3.  Reactive power modes 

This inverter is designed to export active as well as reactive power into the utility grid. The inverter provides several modes of operation for reactive power 

control and are described below:

 

- Disable: This is the default setting. Under this setting, the inverter exports with a power factor of 1.0.

 

- Fixed power factor control (Fixed cos-phi): In this mode, the operator can set the output power factor to a fixed value. When enabled, Set percentage will 

appear on the display, allowing the setting of the value of Cos-Phi as a percentage from 0.1 to 100.

 

- Power factor as function of output power (Std cosphi 0.9): In this mode, the inverter reduces the output power as a function of the output power at a given operating point. 

 

- Dynamic Volt/VAR control (Std Q(U)): In this mode, the level of reactive power exported by the inverter is a function of the operating grid voltage, also 

known as a Volt/VAR curve. 

4.  Power reduction 

This inverter has two modes for active power reduction:

 

- Power limitation: When enabled, this mode limits the active power that the inverter can export to the grid. The setting is specified as a percentage of the 

rated power of the inverter, from 0% to 100% in steps of 1%.

 

- Frequency/Watt function (Set F Derating): In this mode, the inverter limits the active power as a function of the grid frequency. The default frequency/watt 

can be adjusted.

5.  Ramp controls 

The inverter is designed to control the rate at which output power is increased, either at startup, or after a temporary low power condition on the PV array 

(such as fast shading). The following ramp controls are provided on this inverter. 

- Normal ramp: The normal ramp defines the maximum rate at which the inverter can increase the output power under normal operation. The normal ramp 

control limits the dramatic fluctuations in the output power in order to prevent instabilities on the utility grid. The normal ramp rate can be adjusted.

 

- Slow ramp: The soft-start ramp defines the maximum rate at which the inverter can increase the output power when the inverter is first starting up. This 

startup may occur on a daily basis or when the inverter restarts after an abnormal grid event has ended.

Refer to the dedicaterd application note in the ABB Solar website for more details about the grid support functions.

The DC AFD fault circuit interrupter automatically runs a self test every morning when sunlight is sufficient for connection. The inverter display area shows the 

results of the selftest:

- If the self-test results are OK, the inverter will continue with the AC grid connection.

- If a potential problem on the Arc Fault Detection (AFD) board is detected, the self-test will result in an error.

Press the ESC key to clear the error and start the restart selftest. If self-test results are OK, the inverter will reconnect to the AC grid.

If the DC arc fault is still present, the self test will result in error code E050.

Refer to the product manual which must be downloaded at www.abb.com/solarinverters for troubleshooting suggestions.

- During normal operation, the input current is continually measured and analyzed.

- If a DC arc fault is detected, the inverter is disconnected from the AC grid and error E050 will be displayed.

The AFD self-test can be manually started anytime using the following procedure:

1. Turn off the inverter (switching off both DC and AC switches) and,

2. Turn on both the DC and AC switches and wait for the self-test results on the display.

Test Arc Sensor

      OK

Test Arc Sensor

     E053

Test Arc Sensor

     E050

To prevent electrocution hazards, open and lock out the external AC disconnect switch before connecting the AC conductors, and any 

time the AC wiring box cover is to be removed. Proper PPE is required.

AC output overcurrent protection is not provided with the inverter; it is the responsibility of the end user to provide overcurrent protec-

tion for the AC output circuit. To reduce the risk of fire, connect only to a circuit provided with an overcurrent protection in accordance 

with the NEC (ANSI/NFPA 70). The inverter must be connected only to a dedicated branch circuit provided with the maximum branch 

overcurrent protection device (OCPD) listed in the technical data sheet at the end of this document.

Size conductors per the NEC, Article 310 - use 90°C copper wire only; conductors must be sized according to operating temperature 

range and continuous current ratings. The AC grid wiring is connected through the inverter switchbox.

AC output wire must be listed PV wire rated minimum 600V.

- Run an approved raceway between the inverter and external AC disconnect switch.

-  Pass the AC wires throught the openings dedicated to the AC conduit.

When complete, seal conduit with water-tight fittings to maintain the NEMA type 4X enclosure rating.

Installer should follow conduit manufacturers’ guidelines and best practices.

- Determine which AC output is applicable for the inverter model being installed. The AC 

wiring connections based on the AC grid type are shown in the table (also found on a label 

in the wiring box).

208V~

3PH -

240V~

SPLIT-PHASE

GRID ST

AND

ARD

TYPE DE RÉSEAU

TERMINAL

BORNE

WIRE

CÂBLE

L2

L1

N

L1

L3

L2

1

L1

2

L2

3

-

CAUTION

This is a single phase inverter. Use the wiring schemes shown on the
table below when a different grid standard is used. Refer to the
instruction manual to properly set the inverter grid standard from the
front panel display. Use 90°C copper wire only. Refer to the instruction
manual for wiring instructions.

ATTENTION

Ceci est un onduleur monophasé. Utilisez les schémas de raccordement
ci-dessus si le réseau est spécifique. Réferez-vous au manuel
d'installation pour sélectionner via l'afficheur frontal le code pays
adéquat. Utilisez seulement câbles en cuivre 90 °C.
Consulter le manual d'installation pour les instructions de câblage.

AWG# 4 - 8

1

L1

2

L2

3

N

-  Connect wiring to the numbered terminals based on selected grid type. AC wiring terminals are 

spring pressure type and accommodate a wire size range of 20-6 AWG. 

-  Connect the protective earth (PE) cable to wiring box busbar 

16

. Screws  the cable (max 

4 wires 8AWG to 4AWG, copper) with 

2.0Nm (1.5ft-lb)

 torque.

The default 240V split-phase connection requires the grid Neutral to be connected to the inverter for proper operation. Before connecting 

the inverter to the grid, the grid type must be selected during the commissioning phase. If several inverters are installed to a three-phase 

AC grid, always distribute the inverters between the phases in order to reduce power imbalance between the phases.

- When all connections are complete, reinstall the front covers and tighten the cover screws with 

1.5Nm (13.2 in-lbs)

 torque.

CAUTION

ATTENTION

REFER TO LOCAL CODE

FOR WIRE SIZE

FAIRE RÉFERENCE À LA

LÉGISLATION LOCALE POUR

LA DIMENSION DU CABLE

-IN1

+IN1

-IN2

+IN2

1

2

3

-RSD

+RSD

Abnormal grid conditions: 

The inverter is programmed to respond to abnormal grid conditions, as specified in the below table:

Condition

Utility source

Max. time (sec)

2

 at 60Hz before cessation of current

Voltage (V)

Frequency (Hz)

A

<0.50 Vnom

1

Rated (60Hz)

Default setting

3

 0.16 (Adj. 0.16 to 1.5)

B

0.50 Vnom

1

 ≤ V < 0.70

Rated (60Hz)

Default setting

3

 3 (Adj. 0.16 to 30)

C

0.70 Vnom

1

 ≤ V < 0.88

Rated (60Hz)

Default setting

3

 2 (Adj. 0.16 to 30)

C

1.10 Vnom

1

 < (*)

Rated (60Hz)

Default setting

3

 1 (Adj. 0.16 to 30)(*)

D

1.20 Vnom

1

 ≤ V (*)

Rated (60Hz)

Default setting

3

 0.16 (Adj. 0.001 to 0.16 sec)

E

Rated

Default setting

3

 f > 60.5 Hz (Adj. 60.1 to 64.0 Hz)

Default setting

3

 0.16 (Adj. 0.16 to 300 sec)

F

Rated

Default setting

3

 f < 59.3 Hz (Adj. 56.0 to 59.9 Hz)

Default setting

3

 0.16 (Adj. 0.16 to 300 sec)

G

Rated

Default setting

3

 f < 57.0 Hz (Adj. 50.0 to 56.0 Hz)

0.16 (Fixed)

H

Rated

Default setting

3

 f > 63.0 Hz (Adj. 62.0 to 64.0 Hz)

0.16 (Fixed)

1. Vnom is the nominal output voltage rating.

2. Trip limit and trip time accuracy specification is as follows: Voltage: +/-2%, Frequency: +/- 0.10Hz, Time: 2 grid cycles (33ms @ 60Hz).

3. Default settings aligned with IEEE 1547-2003 requirements.

To adjust voltage and frequency and disconnect times to meet local utility requirements, make modifications are made using :

- The inverter embedded web user interface. The Admin password is required to unlock the “installer” functionalities.

- The LCD display. A time-limited service password is required, contact ABB solar inverter technical support 1-877-261-1374.

- Aurora Manager LITE software. Connect the inverter equipped with UNO-DM-COM kit UNO or UNO-DM-PLUS-Ethernet COM kit to a PC through a RS-485/

USB adapter. Download the manual at www.abb.com/solarinverters. An User ID and a password is required to unlock the “installer” functionalities of the software, 

contact ABB solar inverter technical support 1-877-261-1374.

Fault currents and durations:

 During a grid fault including a short circuit condition, the inverter may inject current into the grid as specified below:

Utility voltage (V)

Fault current RMS (A)

1 cycle

3 cycle

5 cycle

208

17.4

15.9

15.8

240

17.1

16.5

16

Output power derating at high ambient temperature: 

Under high ambient temperatures, the inverter is designed to automatically reduce its output power. 

Detailed derating curves by model are provided in the product manual found on www.abb.com/solarinverters.

LED and KEYS

, in various combinations, may display the status conditions or perform complex actions to be explored by consulting the product manual.

LEDs 

06

POWER Green

Solid when the inverter is working correctly. Flashes when checking the grid or 

if there is insufficient sunlight.

COMM 

STATUS Multicolor

Operation status of wireless communication line:

Blink Red

: Communication error (no communication available)

Green

: Communication OK

ALARM

Yellow

The inverter has detected an anomaly. The anomaly is shown on the 

“EVENTS” section of the internal webserver and on the display.

RSSI

Multicolor

Communication type and quality of the wireless communication signal (for “Station 

Mode”):

-  

Blink Blue

: Wireless board is working in Access Point mode (AP Mode)

OFF

: No signal

Blink Red

: Low signal strenght

Blink Yellow

: Medium signal strenght

Blink Green

: High signal strenght

GFI

Red

Ground fault on the DC side of the PV generator. The error is shown on 

the “EVENTS” section of the internal webserver and on the display. 

The LCD has two visible text lines and the UP and DOWN control keys are used to scroll through the menu items. An arrow on the left side of the display highlights 

the current selection. Move the arrow UP or DOWN to the desired selection and press ENTER to access the associated submenu. To return to the preceding menu, 

press the ESC key.

- Press ESC to open the menus. Use the DOWN key to scroll the submenus.

- The default password for Setting menus is 0000.

Keys 

08

ESC

Used to access the main menu, to go back to the previous menu or to go back to the previous digit to be edited.

UP

Used to scroll upwards the menu options or to shift the numerical scale in ascending order.

DOWN

Used to scroll downwards through the menu options or to shift the numerical scale in descending order.

ENTER

Used to confirm an action, to access the main menu or the submenu for the selected option (indicated by the > symbol) or to switch to the next digit to edit.

COMM

STATUS

RSSI

08

07

06

Before proceeding with commissioning, make sure you have carried out all the operations and checks indicated in the previous sections of 

this quick installation guides, and verify that the inverter cover 

05

 was properly closed!

Refer to the product manual for further information about the configuration and the use of the functionality of the internal Webserver.

Commissioning and configuration of the inverter can also be done with the display 

07

. Consult the product manual for more information.

Commissioning and configuration of the inverter can be made using a wireless capable device such as a smartphone, tablet or laptop.

The steps for commissioning a

re listed below:

1.

  Set the inverter’s DC disconnect switch 

16

 and any external DC switches to “ON” position

: If the input voltage applied to one of the two input channels is 

greater than the minimum starting voltage, the inverter will start up.

The inverter is powered ONLY by the voltage coming from the photovoltaic generator: the presence of grid voltage alone IS NOT SUFFI-

CIENT to allow the inverter to power up.

If a RSD device was istalled into the plant, it also will needed to connect the AC grid to allow the inverter to power-up!

2.

  

Set the external AC disconnect switch downstream to the inverter to “ON” position.

 

3.

  Enable Wireless on the device that is being used for the inverter commissioning (tablet, smartphone or PC) and connect it to the Access Point created by the 

inverter: a network with the name 

ABB-XX-XX-XX-XX-XX-XX

 will appear in the list of networks, where “

X

” is a hex digit of the MAC address (MAC address 

can be found on the “Wireless Identification Label” placed on the side of the inverter or previously applied to this quick installation guide - see cover page).

 

4.

  When required enter “

ABBSOLAR

” as network password for the inverter’s access point.

After the inverter has been powered up for 24 hours, the access point default password “ABBSOLAR” will be disabled.

Any subsequent access to the internal webserver will be possible only using the PRODUCT KEY printed on the “Wireless identification 

label” previously applied to this quick installation guide (see cover page) as access point password.

5.

  Open the internet browser (recommended browser: Chrome versions from v.55, Firefox versions from v.50, Safari versions from v.10.2.1) and enter the pre-

set IP address to access the configuration wizard page: 

192.168.117.1 

6.

  A configuration wizard will open, consisting of a sequence of steps in which all the required fields must be completed correctly (language of the wizard can be 

selected in the upper status bar). The steps and information required by the configuration wizard are:

 

 

STEP 1 -

 Set the Administrator/User login credentials (minimum 8 character for password). User and password are CASE SENSITIVE.

 

 

STEP 2 (OPTIONAL) -

 Enter the required information (IP selection mode, SSID and Password) to connect the inverter to the residential wireless network 

with “Station Mode” 

(Note: This step can be skipped to continue operating with the point-to-point connection “AP mode”)

.  Once the inverter is connected to 

the wireless network it will be necessary switch the tablet/smartphone/PC device to the same wireless network to which the inverter is connected to proceed 

with the configuration wizard (for any difficulties concerning this step, refer to the “Internal Webserver and wireless troubleshooting” chapter of the product 

manual).  Once the connection is acquired, a new message will provide you the links (corresponding to the IP Address assigned by the router to the inverter 

and the “Host Name”) that can be used each time you want to access the internal webserver. 

TAKE NOTE OF THEM.

 

 

STEP 3 -

 Set the Date, Time and Time zone (The inverter will propose these fields when available).

 

 

STEP 4 -

 Set the inverter country standard, Input channel configuration and Meter configuration (if installed). Clicking the “END” button the wizard will be 

completed (after confirmation the inverter will reboot).

From the moment that the grid standard is set, you have 24 hours to make any changes to the value, after which the “Country Select” func-

tionality is blocked and the remaining time will have to be reset in order to have the 24 hours of operation available again. To select a new 

grid standard follow the procedure “Resetting the remaining time for grid standard variation” described in the product manual.
Any inverters installed, or commissioned, in California after September 8, 2017 must be set to the Rule 21 country code 

 

USA - RULE21 @ 240 single [R21 240sp] or USA - RULE21 @ 208 single [R21 208si].

Once both AC and DC switches are closed and the wizard commissiong procedure is finished, the inverter starts the grid connection sequence: the inverter 

performs the grid voltage check, measures the PV array insulation resistance against earth and carries out other self-diagnosis checks. 

During the checks before the connection with the grid, the “Power” LED keeps flashing, the “Alarm” and “GFI” LEDs are off. If there is not sufficient sunlight to 

connect to the grid, the inverter will repeat the connection procedure until all the parameters are within range.
 

If the preliminary checks for parallel connection to the grid are successful, the inverter connects to the grid and begins to export power to the grid. 

The “Power” LED remains fixed on while the “Alarm” and “GFI” LEDs are off.

UNO-DM-3.3

UNO-DM-3.8

UNO-DM-4.6

UNO-DM-5.0

Input

Absolute maximum input voltage (V

max,abs

)

600 V

Start-up voltage (V

start

)

default 200 V (120...350 V)

Operating MPPT voltage range (V

dcmin

...V

dcmax

)

0.7xV

start

...580 V (≥ 90V)

Maximum usable power (P

dcrMPPT

) - each channel

2000 W

3000 W

3000 W

3500 W

Number of Independent MPPT 

2

Full power MPPT voltage range (V

MPPT min

 ... V

MPPT max

) with parallel MPPT 

configuration a P

acr

160...530 V (208 Vac)

170...530 V (240 Vac)

120...530 V (208 Vac)

140...530 V (240 Vac)

140...530 V (208 Vac)

150...530 V (240 Vac)

130...530 V (208 Vac)

145...530 V (240 Vac)

Maximum usable current (I

dc max

) - each channel

10.0 A

16.0 A

16.0 A

19.0 A

Maximum current (I

dc max

)

20.0 A

32.0 A

32.0 A

38.0 A

Maximum short circuit current (I

sc max

) - each channel

12.5 A

20.0 A

20.0 A

22.0 A

Number of wire landing terminals

2 pairs, capable of connecting two parallel strings

Array wiring termination

Terminal block, pressure clamp, AWG20-8

Input protection

Reverse Polarity Protection

Yes, from current limited source

Over-voltage protection type

Varistor

PV array ground fault detection

 Pre start-up RISO and dynamic GFDI

DC switch rating (per contact)

600 V / 23A@600V, 38A@500V and 45A@350V

Output

AC grid connection type

1Φ/2W or Split-Φ/3W

Nameplate Apparent Power (S

max

3300 VA (208 Vac)

3300 VA (240 Vac)

4200 VA (208 Vac)

4200 VA (240 Vac)

4600 VA (208 Vac)

4600 VA (240 Vac)

5000 VA (208 Vac)

5000 VA (240 Vac)

Nameplate Output Active Power (P

acr@cosφ=1

)

3300 W (208 Vac)

3300 W (240 Vac)

4200 W (208 Vac)

4200 W (240 Vac)

4600 W (208 Vac)

4600 W (240 Vac)

5000 W (208 Vac)

5000 W (240 Vac)

Output Active Power @V

acr

 and cosφ=±0,9 (P

Rated

)

2700 W (208 Vac)

3000 W (240 Vac)

3000 W (208 Vac)

3450 W (240 Vac)

3780 W (208 Vac)

4140 W (240 Vac)

4118 W (208 Vac)

4500 W (240 Vac)

Nominal AC output voltage (V

acr

)

208Vac (1Φ/2W) or 240Vac (Split-Φ/3W)

Output AC voltage range (V

acmin

...V

acmax

)

183...228Vac (1Φ/2W) or 211...264Vac (Split-Φ/3W)

Maximum current (I

ac max

)

14.5 A

16.0 A

20.0 A

22.0 A

Contributory fault current

16.0 A

19.0 A

22.0 A

24.0 A

Nominal output frequency (f

r

)

60 Hz

Adjustable grid frequency range (f

min

...f

max

)

50...64 Hz

Power factor and adjustability range

>0.995, adj. +/-0.8

Total harmonic distortion at rated power

<2%

Grid wiring termination type

Terminal block, pressure clamp, AWG20-6

Output Protection

Anti-islanding protection 

Meets UL1741 / IEEE1547 requirements

Over-voltage protection type

Varistor, 2 (L1 - L2 / L1 - G)

Maximum AC OCPD rating

20.0 A

20.0 A

25.0 A

30.0 A

Operating Performance

Maximum efficiency (η

max

)

97.0%

97.0%

97.0%

97.4%

CEC efficiency

96.5% (208 Vac)

96.0% (208 Vac)

96.0% (208 Vac)

96.5% (208 Vac)

96.5% (240 Vac)

96.5% (240 Vac)

96.5% (240 Vac)

97.0% (240 Vac)

Stand-by consumption

< 8.0 Wrms

Night-time consumption

< 0.6 Wrms

Auxiliary Output

Isolated Auxiliary Power Supply 

(1)

24Vdc, 0.4A max

Communication

Embedded Communication interface

Wireless 

(2)

Embedded Communication Protocol

ModBus TCP (SunSpec)

Commissioning Tool

Web User interface, Display, Aurora Manger Lite

Monitoring

Plant Portfolio Manager, Plant Viewer, Plant Viewer for Mobile

Optional board UNO-DM-COM Kit

Optional Communication Interface

RS485, Alarm/Load manager relay, Remote ON/OFF

Optional Communication Protocol

ModBus RTU (SunSpec), Aurora Protocol

Optional board UNO-DM-PLUS-Ethernet COM Kit

Optional Communication Interface

Ethernet, RS485, Alarm/Load manager relay, Remote ON/OFF

Optional Communication Protocol

ModBus TCP (SunSpec), ModBus RTU (SunSpec), Aurora Protocol

Environmental

Ambient air operating temperature range 

-13°F to +140°F (-25°C to +60°C) with 

automatic power reduction above 122°F (50°C)

-13°F to +140°F (-25°C to +60°C) with 

automatic power reduction above 113°F (45°C)

Relative Humidity

0-100% RH condensing

Acoustic noise emission level

< 50 db (A) @1m

Maximum operating altitude without derating

6560ft (2000m)

Environmental class

Outdoor

Mechanical specifications

Enclosure rating

Certified to NEMA Type 4X

Cooling system

Natural convection

Dimensions (H x W x D)

34.0 x 16.4 x 6.9in (863 x 418 x 175mm) 

(3)

Weight

33lb (15kg) 

(3)

Shipping weight

46lb (20,7kg) 

(3)

Mounting system

Wall bracket

Conduit connections 

(2)

Bottom: Markings for (2) concentric KOs 1”, 3/4” and (2) KOs 1/2”        Sides: Markings for concentric KOs 1”, 3/4”

Safety

Insulation level

Transformerless (floating array)

Safety and EMC standard

UL1741, IEEE1547.1, CSA-C22.2 N. 107.1-01, UL1998 UL 1699B, FCC Part 15 Class B

Grid standard

UL 1741 SA, IEEE 1547, Rule 21, Rule 14 (HI)

Safety approval

cTUVus

Available models

Model with DC switch, wiring box, AFD, RSD supply output

UNO-DM-3.3-TL-PLUS-US-SB-RA UNO-DM-3.8-TL-PLUS-US-SB-RA UNO-DM-4.6-TL-PLUS-US-SB-RA UNO-DM-5.0-TL-PLUS-US-SB-RA

1. The auxiliary output is used to supply the RSD contactors when required.      2. WLAN IEEE 802.11 b/g/n @2,4GHz      3. When equipped with DC switch and wiring box

Note. Features not specifically mentioned in this data sheet are not included in the product

Отзывы: