Electromagnetic compatibility tests
Description
Type test value
Reference
1MHz/100 kHz burst disturbance
test:
• Communication
• Other ports
Common mide 1kV
Common mode 2.5 k
Differential mode 1.5 kV
GB/T 17626.18-2016 Grade III
(IEC 61000-4-18: 2011)
3 MHz/10 MHz/30 MHz burst
disturbance test:
• Communication
• Other ports
Common mode 1 kV
Common mode 2 kV
IEC 61000-4-18: 2011
Electrostatic discharge test:
• Air discharge
±15 kV
GB/T 17626.2-2018 Grade IV
(IEC 61000-4-2: 2008)
Radio frequency interference
Tests
10V/m, f=80...2700
GB/T 17626.3-2016 Grade III
(IEC 61000-4-3: 2010)
Fast transient disturbance tests:
• Power Supply ports
• Other ports
4 kV
2 kV
GB/T 17626.4-2018 Grade IV
(IEC 61000-4-4: 2012)
Surge immunity test:
• Communication
• Other ports
2 kV, line to earth
4 kV, line to earth
2 kV, line to line
GB/T 17626.5-2018 Grade IV
(IEC 61000-4-5:2005)
Conducted emission immunity
test for RF field induction
10 V (ms)
180 kHz
~ 80MHz
GB/T 17626.6-2017 Grade III
(IEC 61000-4-6: 2013)
Power frequency magnetic field:
• Continuous
• Short term
100 A/m , 60s
1000 A/m, 3s
GB/T 17626.8-2006 Grade V
(IEC 61000-4-8: 2001)
Pulse magnetid field immunity
1000 A/m
GB/T 17626.9-2011 Grade V
(IEC 61000-4-9: 2007)
Magnetic field immunity test of
damped oscillation wave
100 A/m, 2s
Frequency 100 kHz, 1 Mhz
GB/T 17626.10-2017 Grade V
(IEC 61000-4-10: 2001)
Immunity test of voltage sag,
short-term interruption and
voltage change on DC input
power port
40% UT/100 ms
0% UT/50 ms
(IEC 61000-4-11: 2004)
GB/T 17626.29-2006
80% UT/1000 ms
120% UT/1000ms
(IEC 61000-4-29: 2000)
Ripple immunity test on DC input
power port
10% UT, 100Hz, 10 min
GB/T 17626.17-2005 Grade III
(IEC 61000-4-17: 2002)
Conducted emission limit test
• 0.15...0.50 MHz
• 0.5...30 MHz
<79 dB (µV)
quasi-peak value
<66 dB (µV)
average value
<73 dB (µV)
quasi-peak value
<60 dB (µV)
average value
GB/T 14598.16-2002
(IEC 60255-25: 2000)
Radiated emission limit test:
• 30...230 MHz
• 230...1000 MHz
<40 dB (µV/m)
quasi-peak value, measured at 10
meters
<47 dB (µV/m)
quasi-peak value, measured at 10
meters
GB/T 14598.16-2002
(IEC 60255-25: 2000)
Immunity to common mode
conducted disturbances
10V Continuous
IEC 61000-4-16: 2015
100V Short duration
—
5. System technical data