ABB TZIDC Скачать руководство пользователя страница 2

 
 
 

Configuration with Software Rev 1.1 and lower

  

(see other side for Software Rev 2.xx and higher) 

 

5. Switch to the configuration level: 
• Press and hold down 

 and 

 then briefly press and release 

ENTER

• Wait until the countdown from 

to 

is completed. 

• Release 

 and 

The device will automatically go to program level “

P1.0

” 

 
6. Select the actuator type “

ROTARY

” or “

LINEAR

” using

 
Note: Step 6 must be done prior to Autoadjust (Step 7).   

 

7. Start 

Autoadjust

.  Note:  the actuator moves during autoadjust; take necessary precautions & take valve out 

of service. 
• Press and hold 

MODE 

then

 

briefly press 

 until "

P1.1

" is indicated. 

• Release 

MODE

• Press 

ENTER 

and keep it pressed until the countdown from 

to 

is finished. 

• Release 

ENTER 

Autoadjust 

is now activated; the complete process will take a few minutes. 

• When the message "

COMPLETE

" displays to indicate successful Autoadjust, briefly press 

ENTER 

to 

acknowledge. It is also possible that Autoadjust cancels due to errors detected during this procedure; in this 
case, the positioner displays the applicable error message. Refer to Instruction manual for error codes and 
details. 
8. Save the settings: 
• Press and hold 

MODE

 then briefly press 

 until 

P1.4 “EXIT” 

is indicated. 

• Release 

MODE

• Select 

NV_SAVE 

using 

• Press and hold 

ENTER 

until the countdown from 

to 

completes, then release 

ENTER

. The settings are 

saved in the non-volatile memory, and the positioner returns to the last previous operating mode.  To change 
operating mode, see Selecting the Operating Mode section. 
 

Selecting the Operating Mode 

 
Mode 1.1: Fixed control 

• Press and hold 

MODE

 then briefly press 

 as often as required until level 

1.1 “CTRL_FIX” 

displays. 

• Release 

MODE. 

• Positioner is now active in the 

FIXED 

control mode. 

Use Fixed control as the normal operating mode.  Fixed control uses the control parameters determined during 
the autoadjustment procedure.  Note that the positioner does not perform any actuator leakage detection while 
in fixed operating mode. 
 

Mode 1.2: Adaptive Control 

• Press and hold 

MODE

 then briefly press 

 as often as required until level 

1.2 “CTRL_ADP” 

is displayed. 

• Release 

MODE 

• Positioner is now active in the 

ADAPTIVE 

control mode. 

Use Adaptive control if fixed control does not deliver acceptable results.  Adaptive control adjusts positioner 
control parameters during operation as the positioner monitors its control performance at every valve travel 
except for near each end of travel.  The TZID-C in adaptive control minimizes position deviation from signal.  
Note, ABB recommends running in adaptive control for several hours, then switching to fixed control.  Note also 
that the positioner performs actuator leakage detection only when in adaptive control. 
 
Footnote 1. The zero position is automatically determined and saved by the standard autoadjustment function:  
turning counter-clockwise (CTCLOCKW) for linear and clockwise (CLOCKW) for rotary actuators. 

Copyright 2006 ABB, All Rights Reserved [May, 2006] 

 

PN25114 

 