Positioner TZIDC-110 for PROFIBUS PA
Commissioning Instructions
41/18-74 XA
ABB Automation Products GmbH
Schillerstr. 72 · 32425 Minden, Germany
Tel: +49 551 905-534 · Fax: +49 551 905-555
[email protected]
The company’s policy is one of continuous product improvement and the right
is reserved to modify the information contained herein without notice.
Printed in the Fed. Rep. of Germany (02.2009)
© ABB 2009
Commissioning procedure
1.
Turn on the air supply to the positioner.
2.
Connect the bus with arbitrary polarity (or auxiliary power
9 V DC ... 32 V DC) to the bus terminals.
is displayed
If the emergency shutdown module is installed, the supply vol-
tage for this module needs to be 24 V DC (ter85 / -86)
and the switch needs to be in its center position. Otherwise,
the device has no pneumatic function.
3.
Check for proper mounting:
-
Press and hold
M
ODE
and
E
NTER
simultaneously.
Wait until the countdown has run down from 3 to 0, then
release
M
ODE
and
E
NTER
. The operating level
(mode 1.x) is reached and indicated.
-
Press and hold
MODE
. Additionally briefly press or
until mode 1.3 (manual adjustment within the sensor
range) is displayed. Release
MODE
.
-
Press or to move the actuator to its mechanical limit
stops in both directions, and note the values.
Recommended range:
between -28° and +28° for linear actuators
between -57° and +57° for rotary actuators
Minimum angle: 25°
Important:
The positioner should be mounted/adjusted such that the
portions of the sensor’s operating range above and below
the center point are nearly identical. Use the rotation angle
of the position sensor in the positioner to its utmost extent.
4.
Return to the remote level.
-
Press and hold
MODE
and
ENTER
until the count-
down has run down from 3 to 0.
-
Release
MODE
and
ENTER
.
is displayed.
5.
Run the standard Autoadjust function.
-
Make sure that the remote level is activated.
For a
linear
actuator:
-
Press and hold
MODE
until the countdown has run down
from 5 to 0, then release
MODE
.
-
Press and hold
MODE
again until the countdown has
run down from 3 to 0, then release
MODE
.
Standard autoadjustment is started automatically, and the
progress is displayed.
For a
rotary
actuator:
-
Press and hold
ENTER
-
is displayed
-
Wait until the display has changed to
-
Release
ENTER
.
-
Press and hold
ENTER
again until the countdown has
run down from 3 to 0, then release
ENTER
.
Standard autoadjustment is started automatically, and the
progress is displayed.
When standard autoadjustment has completed successfully,
the determined parameters are saved automatically, and the
remote level is activated again.
If, however, an error should occur during standard autoadjust-
ment, error code 255 is briefly indicated.
!
Always observe all safety instructions and
precautions in the operating instructions.
conf
mA
%
C
¬
conf
mA
%
C
¬
conf
mA
%
C
¬
conf
mA
%
C
¬
The device then automatically changes over to parameter P1.1
Autoadjust at the configuration level. In this case:
- Press and hold
MODE
. Additionally, briefly press or seve-
ral times until P1.6 “EXIT” is displayed.
- Release
MODE
. CANCEL is displayed. If not, briefly press
or .
- Press and hold
ENTER
until the countdown has run down from
3 to 0.
The positioner automatically returns to the operating level. Briefly
press twice to reach operating mode 1.3 “Manual adjustment
within the sensor range” and then check the positioner-actuator
assembly for proper mounting. Re-adjust if required (see operating
instructions for details) and then start standard autoadjustment
again.
Operating modes
Prodecure for mode selection from operating level:
•
Press and hold
MODE
. Additionally briefly press as often
as required. The selected operating mode is indicated.
•
Release
MODE
.
The position is indicated as a percentage
or rotation angle
Overview:
*) Positioning is not active.
**)For quick motion: press
and
together.
Setting the bus address
•
From remote level: Change over to the operating level. Press
and hold
MODE
and
ENTER
simultaneously until the
countdown has run down from 3 to 0. Release
MODE
and
ENTER
.
•
Switch to the configuration level: Press and hold and
simultaneously. Additionally, briefly press
ENTER
once.
Keep and pressed until the countdown from 3 to 0 is fin-
ished (approx. 3 seconds). Do not release earlier. P1._
"STANDARD" is displayed.
•
Set the bus address: Press and hold
MODE
.
Additionally
briefly press or until P1.5 "ADDRESS" is displayed.
Release
M
ODE
. “126, ADDRESS” is displayed (factory
setting). Press or to increment or decrement this bus
address.
•
Save the bus address: Press and hold
ENTER
until the
countdown has run down from 3 to 0. Release
ENTER
. Then
press and hold
MODE
. Additionally press or as often as
required to call P1.6 "EXIT". Press or to set this parame-
ter to NV_SAVE.
•
Return to the operating level:
Press and hold
ENTER
until
the countdown has run down from 3 to 0.
•
Return to remote level:
Press and hold
MODE
and
ENTER
until the countdown has run down, then release.
Mode
Mode display
Position display
1.1 Positioning with fixed
setpoint; setpoint adjust-
ment via or .
1.2 Manual adjustment *
within the operating range.
Press or to adjust. **
1.3 Manual adjustment *
within the sensor range.
Press or to adjust. **
conf
mA
%
C
¬
conf
mA
%
C
¬
conf
mA
%
C
¬
conf
mA
%
C
¬
conf
mA
%
C
¬
conf
mA
%
C
¬