2
Electrical characteristics
Supply voltage:
230 V AC ± 15%
Frequency: 50/60
Hz
Power consumption:
max. 6 VA to 50 Hz
Output TWA-1:
1 changeover volt free contact.
Output TWA-2:
2 changeover volt free contacts.
Maximum load:
AC1
µ16A 250 V~
Cos
φ
= 0,6
µ10A 250 V~
Minimum current:
AC1
100 mA 250 V~
Galvanic insulation between power supply and output: < 4 kV
Functional characteristics
Programming capacity: 56 steps to be distributed on the 2 channels.
Minimum time between 2 steps: 1 minute
Running accuracy: ± 1,5 Sec / 24 h
Astronomical time accuracy: ±10 minutes
Operating reserve: lithium battery provides 5 years of backup.
The product is set in standby mode (display is off) if power goes off.
It is set back in
auto
mode when power is back on. With power off, the screen
display is turned on when striking any key. After one minute, it is turned off.
Protection degree: IP 20
The products need to be protected according to the standards NFC 15 100
and/or IEC60 364-1
Operating temperature: -10 °C to +55 °C
Storage temperature: -20 °C to +60 °C
230 V
2300 W
2300 W
500 W
compensated //
(max. 45 µF)
400 W
non compensated,
compensated
in series
1000 W
Lighting
loads