Electrical
connection
CI/TTH300-EN
TTH300
EN - 17
4.3.2 Installation in ignition protection areas
Transmitters can be installed in a wide variety of industrial sectors. Systems that require ignition
protection are divided into zones. As a result, different instruments are also required. For
additional information, refer to the section “Explosion-protection relevant information” or the data
sheet.
4.3.2.1 Zone
0
Transmitter design: II 1G EEx ia IIC T6
Zone 0
Explosion-protection zone 0
Safety area
B
C
ia
A00145
ia
J
A
D
i
a
Fig. 12
A Sensor
B Transmitter in housing with IP20 level of
protection
C Power supply [EEx ia]
D HMI interface for LCD displays (activation
is possible as an option only when
ordering)
For instruments in zone 0, the transmitter must be installed in its own housing with IP20 level of
protection. The input for the power supply must be in [EEx ia] design.
When using the transmitter in zone 0, make sure you prevent electrostatic charging of the
temperature transmitter (observe warnings on equipment).
The sensor must be used by the user in accordance with applicable ignition-protection
standards.