Ex relevant specifications
32 - EN
TTF300
CI/TTF300-X1
5.4
TTF300-E5X, non-sp dust explosion
protection ATEX
Explosion protection
Approved for use in Zone 2 and Zone 22
Designation
II 3G Ex nA II T6
II 3 D IP 65 T 135 °C
ABB manufacturer's declaration in accordance with ATEX Directive
Temperature table
Temperature
class
Device category 3 use
T6
-50 … 56 °C (-58 ... 132,8 °F)
T5
-50 … 71 °C (-58 ... 159,8 °F)
T4
-50 … 85 °C (-58 ... 185,0 °F)
5.5
TTF300-D1X, dust explosion protection ATEX
Explosion protection
Approved for use in Zone 20
Designation
II 1D Ex tD A20 IP66 T135°C
EC type-examination test certificate BVS 06 ATEX E 029
5.6
TTF300-D2X, dust explosion prot
intrinsic safety ATEX
Explosion protection
Approved for use in Zone 20 and Zone 0
Designation
II 1D Ex tD A20 P66 T135°C
II 1G Ex ia IIC T6
EC type-examination test certificate BVS 06 ATEX E 029
EC type-examination test certificate PTB 05 ATEX 2017 X
EC type-examination test certificate PTB 05 ATEX 2016 X
5.7
TTF300-E3X, flameproof enclosure ATEX
Explosion protection
Approved for use in Zone 1
Designation
II 2G Ex d IIC T6
EC type-examination test certificate PTB 99 ATEX 1144
5.8
TTF300-E4X, flameproof enc
intrinsic safety ATEX
Explosion protection
Approved for use in Zone 1
Designation
II 2G Ex d IIC T6
II 1G Ex ia IIC T6
EC type-examination test certificate PTB 99 ATEX 1144
EC type-examination test certificate PTB 05 ATEX 2017 X
EC type-examination test certificate PTB 05 ATEX 2016 X
5.9
TTF300-L1X, intrinsically safe FM
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, AEx ia IIC
TTF300-L1H: Control Drawing: SAP_214832
TTF300-L1P: Control Drawing: TTF300-L1..P (IS)
TTF300-L1F: Control Drawing: TTF300-L1..F (IS)
5.10 TTF300-L2X, non-incendive FM
Class I, Div. 2, Groups A, B, C, D
Class I Zone 2 Group IIC T6
TTF300-L2H:
Control Drawing: SAP_214828
Control Drawing: SAP_214830
TTF300-L2P:
Control Drawing: TTF300-L2..P (NI_PS), TTF300-L2..P (NI_AA)
TTF300-L2F:
Control Drawing: TTF300-L2..F (NI_PS), TTF300-L2..F (NI_AA)
5.11 TTF300-L3X, explosion proof FM
XP,NI, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
5.12 TTF300-L7X, explosion proof +
intrinsically safe FM
XP, NI, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, AEx ia IIC T6
TTF300-L1H: Control Drawing: SAP_214832
TTF300-L1P: Control Drawing: TTF300-L1..P (IS)
TTF300-L1F: Control Drawing: TTF300-L1..F (IS)
5.13 TTF300-R1X, intrinsically safe CSA
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, Ex ia IIC
TTF300-R1H: Control Drawing: SAP_214825
TTF300-R1P: Control Drawing: TTF300-R1..P (IS)
TTF300-R1F: Control Drawing: TTF300-R1..F (IS)
5.14 TTF300-R2X, non-incendive CSA
Class I, Div. 2, Groups A, B, C, D
TTF300-R2H:
Control Drawing: SAP_214827
Control Drawing: SAP_214895
TTF300-R2P:
Control Drawing: TTF300-R2..P (NI_PS), TTF300-R2..P (NI_AA)
TTF300-R2F:
Control Drawing: TTF300-R2..F (NI_PS), TTF300-R2..F (NI_AA)
5.15 TTF300-R3X, explosion proof CSA
XP,NI, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
5.16 TTF300-R7X, explosion proof +
intrinsically safe CSA
XP,NI, DIP Class I, II, III, Div. 1 + 2, Groups A-G, factory sealed
Class I, Div. 1 + 2, Groups A, B, C, D
Class I, Zone 0, Ex ia Group IIC T6
TTF300-R1H: Control Drawing: SAP_214825
TTF300-R1P: Control Drawing: TTF300-R1..P (IS)
TTF300-R1F: Control Drawing: TTF300-R1..F (IS)