TruFit™
Power Distribution Unit│94-1100-00002874 A0 EN 71
6.2
Electrical characteristics
Table 6-1: Electrical characteristics
kVA
Voltage
Full Load Amps
Main Breaker Rating,
Frame
50
480
61
125 AMP
75
480
91
125 AMP
125
480
151
250 AMP
150
480
181
250 AMP
225
480
271
400 AMP
300
480
362
600 AMP
6.3
Environmental characteristics
The PDU has the capability of withstanding any combinations of environmental conditions listed below
without mechanical or electrical damage or degradation of operation.
Operating ambient temperature: 0 to 40° C
Non-operating and storage ambient temperature: -25 to 55° C
Noise level, Per NEMA ST-20:
o
<50dbA (up to 150kVA)
o
<55dbA (up to 300kVA)
Barometric pressure: At elevations up to 3300 feet above sea level
Equipment is designated for indoor use in a clean (dust-free), temperature and humidity-controlled
environment