 ABB Transformer Protection Unit 2000R

4-5

Relay Design and Specifications

Installation

The TPU-2000R unit comes enclosed in a metal case. Follow the instructions and diagrams in this section to
install the TPU-2000R.

Receipt of the TPU-2000R

When you receive the TPU-2000R, examine it carefully for shipping damage. If any damage or loss is evident, file a
claim at once with the shipping agent and promptly notify the nearest ABB sales office.

Before installing the unit, it is suggested that the following procedures be performed:

On units equipped with an MMI

• Power up the relay.  The LEDs should light and a slight clicking sound will be heard.

• Using the arrow keys, go to the Main Menu, scroll to Settings,  press <E>, scroll to Unit Information, press <E>.  Verify

unit information against front panel nameplate.

• Press <C> to return to the Settings menu, scroll to Show Settings, press <E>.  Check default settings against the tables

supplied in this manual.

• After checking the default settings, press <C> twice to return to the Main menu.  Scroll to Test and press <E>, at the

Self Test selection, press <E>.  The unit will self test.

• After performing the self test, press <C> twice to return to the Main menu.  Scroll to Settings and press <E>, in the

Settings menu, scroll to Change Settings and press <E>. In the Change Settings menu, scroll to Clock, and set the
unit clock.

• At this point, the internal battery is now in use.  If the unit is not going into service for an extended period, set the day

of the month to zero (0) and the battery will not be in use.  The battery will remain unused until the clock is set to a
valid date.

• Press <E> to enter the correct time and return to the Change Settings menu.

• Set the PASSWORD by scrolling to Configuration and press <E>.  At the Password prompt, press <E> again. Once

in the Change Confi Sett  menu, scroll to Relay Password and enter a password.  This will be the main password for
entry to the unit. Press <E> to enter the password and return to the Change Confi Sett menu.  Scroll to Test Password,
and enter a different password.  This password allows low level entry to the Test options of the unit.

WARNING:

If the password entered in the Relay Password section is lost or forgotten, the unit cannot be
accessed.  If this situation occurs, contact ABB Allentown immediately.

On units not equipped with an MMI, connect a PC to the RS-232 port on the front of the unit and use the ECP
(External Communication Program) and follow the same process as outlined above.

Installing the TPU-2000R

The TPU-2000R is enclosed in a standard 3U (3 unit high rack), 19 x 5-inch case designed for rack mounting. Figure
4-2 shows the dimensions of the TPU-2000R.  A kit for panel mounting can be ordered separately.  See section 13 for
details.

Содержание TPU2000R

Страница 1: ...nd press E In the Change Settings menu scroll to Clock and set the unit clock At this point the internal battery is now in use If the unit is not going into service for an extended period set the day of the month to zero 0 and the battery will not be in use The battery will remain unused until the clock is set to a valid date Press E to enter the correct time and return to the Change Settings menu...

Страница 2: ...57 2 5 22 132 6 C E 594 15 1 STATUS NORMAL FAIL OVERTEMP OVERLOAD SYSTEM RESET A B C N DIFFERENTIAL TIME INSTANTANEOUS NEGATIVE SEQUENCE TARGET RESET TARGETS TPU 2000R RET 544 G 2 Top View 9 00 229 0 17 12 434 8 15 4 1 625 42 Bracket Position for Semi flush Mounting Bracket Position for Flush Mounting Figure 4 2 TPU 2000R Case Dimensions ...

Страница 3: ...he table Jumper 6 is used to set the TRIP Output Contact to Normally Open or Normally Closed Figure 4 3 Rear Terminal Block SENSOR 7 CONT INST BOOK SERIAL NO CATALOG NO TYPE GRD PHASE FREQ COM 1 COM 2 VN VC VB VA SENSOR 8 IN 1 VDC COM MON IN 2 IN 3 IN 4 IN 5 5 7 4 AUX PORTS 1 2 3 5 6 5 5 5 5 8 6 6 0 5 9 6 1 7 6 2 8 6 4 6 3 IN 6 IN 7 IN 8 3 1 3 2 3 3 3 4 3 9 4 0 4 1 SELF CHECK ALARM 1 1 9 1 0 1 2 1...

Страница 4: ... Press CR to continue The next screen to appear will be the Main Menu If com settings are not compatible or some other problem exists the Communication Status screen appears Reset the com settings and recheck connections and press CR The only option necessary for downloading the software update is the Update Unit Software selection Using the arrow keys scroll to the Update Unit Software selection ...

Страница 5: ...r Editor Access Status involved The 1 s in the bit pattern indicate where a failure has occurred Count from the right of the bit pattern starting with zero to the position where a 1 occurs Compare that bit position with Table 4 1 to reveal the failure See the following examples for further explanation If the self test fails the TPU 2000R is no longer providing protection Replace the unit as soon a...

Страница 6: ... table are stored in nonvolatile memory preventing data loss during control power cycling When you finish editing any settings table the changed table s data is transferred from a temporary edit buffer into three separate locations in nonvolatile memory A background diagnostics task continuously runs a checksum on each copy of the settings tables to verify data consistency If an invalid copy is de...

Страница 7: ...o reset LED targets and the LCD after a fault push C once scroll through all metered values push C twice reset the peak demand values push C three times Perform a system reset by simultaneously pressing the C E and up arrow keys This resets the microprocessor and re initiates the software program During a system reset no stored information or settings are lost The following displays and menus are ...

Страница 8: ...ings Alt2 Settings Configuration Counter Settings Alarm Settings Clock Communications RECORDS MENU Diff Fault Record Through Fault Record Operations Record Operations Summary SETTINGMENU Show Settings Change Settings Unit Information Password protected MAIN MENU Meter Settings Records Operations TEST MENU Self Test Contact Inputs Output Contacts UNIT INFORMATION CAT 588R0411 6111 SERIAL 951280 CPU...

Отзывы: