CU R R E NT  A N D  VOLTAG E  I N STRU M E NT  TR A N S FOR M E R S

I N S T R U C T I O N S  FO R  I N S TA L L AT I O N ,  USE  A N D  M A I N T EN A N C E

Where:

1VLT5216000812

serial barcode

TJC 4

transformer type code

6000

3//100/

 

3/100/3 V

rated voltage ratio

a-n

terminal marking for measuring 
secondary winding

da-dn

terminal marking for residual 

(open-delta) winding

0.5; 3P

accuracy classes

10 VA 

rated output

1.9xUn/8h

overvoltage factor

12/28/75 kV

highest voltage for equipment / 
power-frequency
withstand voltage / rated lightning-
impulse voltage

400 VA

rated output

50 Hz

rated frequency

40°C

ambient temperature

IEC 61869-3

referred standard

E

temperature class

2016

year of production

3. Instructions for installation

General informations

Instrument transformer is an electrical equipment 
and the electrical installation shall be done by 
skilled person only. National legislation can set 
down the minimum age and the criteria for com-
petence of skilled persons working on, with, 
or near an electrical installation.

Where is not the national legislation requirements 
for competence, the criteria shall be used at least 
according to EN 50110-1.

Safety instructions

1.  Always consider transformer as a part of the 

cir  cuit to which it is connected, and do not 
touch the leads and terminals or other parts 
of the transformer unless they are known to 
be grounded.

2.  Always ground the metallic bases of instru-

ment transformer. 

3.  Always ground one secondary terminal of the 

transformer, except if the windings of voltage 
transformer are connected to open delta. Re-
sidual voltage windings connected to open 
delta must have dn terminal earthed only on 
one of three transformers (earthing screws at 
dn terminals of others two transformers have 
to be removed). When the secondary of trans-
former is interconnected, there should be only 
one grounded point to prevent accidental par-
alleling with system grounding wire. In case of 
disconnection from the ground, the ground-
ing screw has to be removed from the second-
ary terminal. Connection between secondary 
terminal and base plate (ground) is shown on 
the picture “Crossection of double line termi-
nal box“

4.  Always short-circuit the secondary of the cur-

rent transformer, which is not currently in use 
to prevent secondary voltages which may be 
hazardous to personnel or damaging to the 
transformer’s secondary. The secondary like 
this must be additionally grounded.

5.  Never short-circuit the secondary terminal of 

a voltage transformer even this is not in use. A 
secondary short-circuit will cause the unit to 
overheat and fail in a very short period of 
time.

6.  Protection of single pole insulated voltage 

transformers against feroresonance phenom-
ena is stated in Appendix 3. – Damping of the 
ferroresonance in Voltage transformers type 
range TJx. 

7.  In case of the current transformer with volt-

age indication (coupling electrode included) is 
secondary terminal box equiped with PE ter-
minal, which is connected with earthing screw 
to the base plate, which must be generally 
earthed. Connection between secondary ter-
minal and base plate is shown on the picture 
“Crossection of single line terminal box“ 

02 Example of voltage 

transformer label


02

Содержание TPU Series

Страница 1: ...MEDIUM VOLTAGE PRODUCTS Current and Voltage Instrument Transformers Instruction for Installation use and maintenance...

Страница 2: ...7 Capacitive voltage indicator divider 7 Fuses 7 4 Instructions for use 8 Routine test report 8 5 Instructions for maintenance 8 6 Transport Storage 8 7 Disposal 8 8 Handling with the transformer 8 9...

Страница 3: ...er type code or n 544234 order number 150 300 5 5A CD rated transformer ratio capacitive divider 50 Hz rated frequency 1S1 1S2 terminal marking for core number 1 first tap 1S1 1S3 terminal marking for...

Страница 4: ...age transformer are connected to open delta Re sidual voltage windings connected to open delta must have dn terminal earthed only on one of three transformers earthing screws at dn terminals of others...

Страница 5: ...ific transformer type The mounting position of the indoor transformer can be freely chosen The transformer is fixed us ing the mounting base with four screws M10 and washers Fastening must be done on...

Страница 6: ...al cover is sealable Degrees of IP protection Indoor transformers IP40 or IP30 for transformers TTR BB KOKS Max Tightening torque Nm Min Tightening torque Nm M5 3 5 2 8 M6 4 3 Tab 2 The maximum permis...

Страница 7: ...s Warning All VT s type TJP 4 0 TJPH 4 0 TJP 5 0 TJPH 5 0 TJP 6 0 have fuse contact equipped with fixation Fuse contact fixation is used just for transportation Before installation must be removed See...

Страница 8: ...us envi ronmental impact and materials are not toxic Disposal of instrument transformers is controlled by national legislation of communal waste 8 Handling with the transformers Handling with the tran...

Страница 9: ...h CD 4 cores 4 cores with CD 5 cores One core One core with CD Two cores Two cores with CD Variants of connections double row terminal Special CT according Ck s1 s2 s1 s2 PE Ck s1 s2 s3 s1 s2 s3 PE Ck...

Страница 10: ...2 measuring winding with tap 1 measuring winding with no tap 1 measuring winding with 1 tap 1 measuring residual 2 measuring winding with no tap 2 measuring winding with 1 tap 2 measuring residual 3 m...

Страница 11: ...y2 z2 Ck No tap x1 x2 y1 y2 z1 z2 x1 y1 z1 PE x2 x3 y3 z2 z3 x2 x3 y3 z2 z3 Ck 1 tap x1 y1 y2 z1 x1 y1 y2 z1 PE x2 x3 y2 y3 z2 z3 x2 x3 y2 y3 z2 z3 Ck 2 taps x1 x4 y1 y4 z1 z4 x1 x4 y1 y4 z1 z4 PE x3...

Страница 12: ...PE x2 x3 y2 y3 z2 z3 x2 x3 y2 y3 z2 z3 Ck 2 taps x1 x4 y1 y4 z1 z4 x1 x4 y1 y4 z1 z4 PE x3 x4 x5 y4 y5 z4 z5 3 taps x1 x2 y1 y2 y3 z1 z2 z3 Three cores Three cores with CD x1 x2 H2 PE x1 x2 x3 H2 PE x...

Страница 13: ...Primary current High Ratio Low Ratio P1 P2 1S1 1S2 1S3 Primary current P1 P2 Secondary current 1S1 1S2 Secondary current 2S1 2S2 P1 C1 C2 P2 Secondary current S1 S2 Primary voltage Secondary voltage...

Страница 14: ...14 CURRENT AND VOLTAGE INSTRUMENT TR ANSFORMERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE Examples of current transformers connection...

Страница 15: ...15 Examples of voltage transformers connection...

Страница 16: ...c or with fundamental frequency or aperiodic Using damping resistor or VT Guard in the residual voltage secondary shown in figure below can considerably reduce the risk for ferroresonance There is an...

Страница 17: ...crane Note This system is recommended for types TTR TSR BB O KOKS Hanging systems for those types are visualized on pictures Safety warning Lifting capacity of the belts and the crane has to be at lea...

Страница 18: ...TPU TPE IHBF KOFA This handling system is vi sualized on the picture Safety warning Lifting capacity of the hooks and the crane has to be 200 kg at least Always make sure that the hooks hold safely on...

Страница 19: ...ck to a body of transformer 2 Screwdriver procedure It is recommended to use a screwdriver to punc ture a hole in a secondary terminal cover A screwdriver shall be placed to a weakened place close to...

Страница 20: ...4 5 7 1 2 3 4 1 3 TPU 4 5 8 1 2 3 4 1 3 TPU 4 5 0 3 11 TPU 4 5 0 12 TPU 4 5 4 5 6 7 8 11 TPU 4 5 0 3 13 TPU 4 5 0 14 TPU 4 5 4 5 6 7 8 13 TPU 4 5 0 3 21 TPU 4 5 0 22 TPU 4 5 4 5 6 7 8 21 TPU 4 5 0 3 2...

Страница 21: ...M12 M8 TPU 60 12 TPU 60 14 TPU 60 22 TPU 60 24 80 80 32 120 40 20 M12 TPU 64 11 TPU 64 13 TPU 65 11 TPU 65 13 TPU 66 11 TPU 66 13 TPU 67 11 TPU 67 13 TPU 68 11 TPU 68 13 TPU 60 3 11 TPU 60 12 TPU 64...

Страница 22: ...VOLTAGE INSTRUMENT TR ANSFORMERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE 280 407 6 a 178 1 4 235 25 375 150 455 110 80 80 32 120 40 20 M12 TPU 64 68 21 TPU 64 68 23 a mm 340 Dimensional Dra...

Страница 23: ...32 120 40 20 M12 260 390 a 250 350 220 15 150 295 14 70 80 32 120 40 19 M12 TPU 74 41 TPU 74 43 TPU 75 41 TPU 75 43 TPU 76 41 TPU 76 43 110 80 40 32 120 20 M12 TPU 70 41 TPU 73 41 68 60 32 120 18 M12...

Страница 24: ...24 CURRENT AND VOLTAGE INSTRUMENT TR ANSFORMERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE Dimensional Drawings TPE...

Страница 25: ...25 Dimensional Drawings TTR TTR 4x xx TTR 6x xx...

Страница 26: ...26 CURRENT AND VOLTAGE INSTRUMENT TR ANSFORMERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE Dimension Weight kg Type Dimensional Drawing BB BB 103 BB 104 BB 223...

Страница 27: ...M10 M5 TERMINAL MUST BE CONNECTED TO THE PRIMARY BAR Drawing n Polarity 44402540 P1 to secondary terminal 44402550 P2 to secondary terminal KOKS 12A41 KOKS 17 5A41 WEIGHT 42kg Dimensional Drawings KOK...

Страница 28: ...28 CURRENT AND VOLTAGE INSTRUMENT TR ANSFORMERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE Dimensional Drawing KOKS 24 KOKS 24...

Страница 29: ...nce 220 mm Arcing distance 210 mm KOFA 12 B1 D1 KOFA 12 B2 D2 F2 KOFA 12 B3 D3 F3 KOFA 24 B1 D1 KOFA 24 B2 D2 F2 KOFA 24 B3 D3 F3 KOFA 12 A3 KOFA 12 C3 KOFA 12 E3 KOFA 24 A3 KOFA 24 C3 KOFA 24 E3 Weig...

Страница 30: ...ANSFORMERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE Dimensional Drawings IHBF Weight appr 19 kg Weight appr 14 kg IHBF 12 A IHBF 17 A IHBF 24 C IHBF 24 B IHBF 12 B IHBF 17 B Weight appr 27 k...

Страница 31: ...31 Transformers with base plate clamp type secondary terminals IHBF 12 A IHBF 17 A IHBF 24 C IHBF 12 A IHBF 17 A IHBF 24 C Weight appr 14 kg Weight appr 14 kg...

Страница 32: ...S FOR INSTALL ATION USE AND MAINTENANCE Dimensional Drawings TJC A M10 E C B G D F H TJC 4 5 TJCH 4 5 TJC 6 TJC 7 1 A mm 220 282 324 B mm 338 352 393 C mm 148 178 250 D mm 270 275 300 E mm 125 150 225...

Страница 33: ...8 M8 Pg16 14 308 314 4 55 324 6 0 45 70 R 1 5 M10 192 420 15 360 45 150 178 250 150 107 4 x 1 4 Drawing n 1VL4200515R0101 TJC 7 1 WEIGHT 48kg CREEPAGE DISTANCE 398mm Weight 48 kg Creepage distance 398...

Страница 34: ...ERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE 190 5 130 250 441 M8 340 450 29 39 72 Pg16 14 M10 420 160 4x 12 85 15 155 15 107 160 Drawing n 44203800 TJC 7 WEIGHT 50kg CREEPAGE DISTANCE 480mm...

Страница 35: ...8 33 30 130 M8 M10x16 Pg16 14 4 170 280 169 178 R7 352 2x 14 10 275 12 150 14 30 150 138 107 Drawing n 1VL4200396R0101 TJCL 6 WEIGHT 25kg CREEPAGE DISTANCE 326mm Weight appr 25 kg Creepage distance 32...

Страница 36: ...6 107 15 12 120 Drawing n 1VL4200252R0101 TJE 3 TJE 4 WEIGHT 10kg CREEPAGE DISTANCE 245mm 202 103 94 4 28 38 54 M8 M10 Pg16 14 120 190 70 125 125 148 2x 11 11 145 125 107 11 270 11 10 338 TJE 3 1 TJE...

Страница 37: ...25 45 605 324 10 275 11 12 164 178 107 248 18 max fuse IEC 60282 1 41 OPTIONAL FOR CABLE CONNECTION CREEPAGE DISTANCE 566mm M8 Drawing n 44204070 Drawing n 1VL4200419R0101 TJP 6 0 WEIGHT 42kg CREEPAGE...

Страница 38: ...42 kg Creepage distance 342 mm 240 49 277 5 307 356 489 209 4 28 38 27 20 133 201 20 max 14 Pg16 125 148 10 270 334 40 75 2x 11 25 12 11 M8 Drawing n 1VL4200251R0101 TJP 4 0 F WEIGHT 24kg CREEPAGE DIS...

Страница 39: ...39 Weight 43 kg Creepage distance 536 mm TJP 6 0 G with long baseplate Weight appr 42 kg Creepage distance 536 mm TJP 6 0 G...

Страница 40: ...30 45 70 107 393 300 30 696 4x 14 225 250 100 84 25 54 18 max A fuse IEC 60282 1 Drawing n 1VL4200508R0101 TJP 7 0 WEIGHT 53kg CREEPAGE DISTANCE 745mm TJP 7 1 Weight appr 54 kg Creepage distance 745 m...

Страница 41: ...41 A M10 E C G I D F B J H TDC 4 5 TDC 6 A mm 220 280 B mm 338 352 C mm 148 178 D mm 270 275 E mm 125 150 F mm 11 11 G mm 110 130 H mm 100 165 I mm 88 60 J mm 11 14 Dimensional Drawings TDC TDC 4 5 6...

Страница 42: ...42 CURRENT AND VOLTAGE INSTRUMENT TR ANSFORMERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE Weight 72 kg Creepage distance 334 mm TDC 7...

Страница 43: ...4 1 fuse JT6 300 mA fuse JT6 600 mA Weight 29 kg TDP 6 1 fuse JT6 300 mA fuse JT6 600 mA Weight 38 kg TDP 4 2 fuse IEC 600282 1 Weight 29 kg TDP 6 2 fuse IEC 600282 1 Weight 38 kg Dimensional Drawing...

Страница 44: ...44 CURRENT AND VOLTAGE INSTRUMENT TR ANSFORMERS INSTRUCTIONS FOR INSTALL ATION USE AND MAINTENANCE KGUG 24 KGUG 36 Dimensional Drawings KGUGI and KGUG...

Страница 45: ...5 220 340 32 78 4x 11 72 14 P P M1 1 M8 Drawing n 1VL4200392R0101 KGUGI 24 WEIGHT 60kg 230 248 79 40 72 8 Pg 16 348 2 427 2 45 443 227 10 155 505 380 245 95 186 300 37 443 78 77 4x 11 14 P P M1 1 M8 D...

Страница 46: ...175 10 fuse JT6 300 600mA EXTERNAL FUSE COVER 17 5kV External fuse holder up to 17 5 kV 35 346 49 4 75 8 M8 175 10 fuse JT6 300 600mA EXTERNAL FUSE COVER 25kV External fuse holder up to 25 kV fuse JT6...

Страница 47: ...le lack of information in this document We reserve all rights in this document and in the subject matter and illustrations con tained therein Any reproduction disclosure to third parties or utilizatio...

Отзывы: