  The remaining tabs (Flash Loader, PIC Loader and Test) can 

be left at their default settings. 

Step 8  

Configuring the WellTell-IS 

Just as the host radio, WellTell-X, was configured, it is necessary to 

configure the WellTell-IS client radio. 

As with the WellTell-X, it is necessary to have the WWU program and a 

typical 9-pin to 9-pin (male DB9 to female DB9) cable. The cable 

connects between the laptop and the maintenance connector on the 

WellTell-IS. 

The opening screen for the WellTell-IS client radio is similar to the 

opening screen for the WellTell-X host, with the exception of a display 

that states that this is a Wireless Client Server as opposed to a Wireless 

Host Server. 

Rather than providing an in-depth, screen-by-screen explanation of the 

WWU, please refer to Figure 10 to view the available tabs. As with the 

previous section, the following details each individual tab available to the 

user and the corresponding parameter fields and values that must be 

entered therein. 

8A

  System Config tab – Set the parameters as shown in Figure 

10. 

8B

  Radio Config tab – Set the parameters as follows: 

Parameter Field 

Value 

Mode Client 
Network ID 

1 (Must match Host 

RF Channel 

Anything between 16 and 47 
(must match Host) 

Baud Rate 

9600 

Delivery Mode 

Broadcast 

RF Mode 

Acknowledge 

Duplex Mode 

Half Duplex 

8C

  Network View tab – These parameters should be left at their 

default settings. 

8D

  PC Port tab – Set the parameters as follows: 

Parameter Field 

Value 

Port 

COM 1 (Communication port of laptop PC) 

Baud Rate 

9600 

Data Bits 

7 or 8 bits based on user setup 

Parity 

Odd/Even/None depending on user setup. 

Stop Bits 

Содержание TOTALFLOW WellTell Wireless IS

Страница 1: ......

Страница 2: ...y It is recommended that inexperienced technicians consult the Totalflow WellTell Wireless User s Manual for more detailed information while performing the installation and start up The Totalflow WellTell wireless product is designed to replace expensive cable with robust and inexpensive radio links Cable trenching presents drawbacks related to expense inconvenience maintainability and safety Spre...

Страница 3: ...wo Level Master sticks NOTE See larger detailed figures Figure 1 Basic Setup Basic Installation The following information covers the initial installation of the WellTell X host at the site controller XFC XRC the installation of the WellTell IS client near the LevelMaster application and the final application configuration and test at the site controller The instructions are broken down into segmen...

Страница 4: ...re 2 Place the level against the pipe and vertically align Adjust the pipe mounted in the saddle until vertical alignment is achieved After vertical alignment securely tighten the 2 by 40 pipe in the saddle Tighten the saddle mounting bolts Ascertain that the pipe is securely installed in the saddle 1C Position the enclosure on the 2 mounting pipe and secure in place with two U bolts flat washers ...

Страница 5: ...flow 6400 or 6700 enclosure see Figure 4 At the top of the enclosure is the area where communication devices are installed This area is referred to as the communication compartment see Figure 5 All communication equipment is secured to the communication tray and slid into this compartment The WellTell X is mounted to standoffs on the communication tray and then slid into the communication compartm...

Страница 6: ...4 Figure 4 Communication Tray Figure 5 Communication Tray Installed in the 6700 Enclosure ...

Страница 7: ...mple uses COM 2 of the XFC COM 1 is often defaulted for communication with a remote device radio modem etc Wiring is simplified by the use of pre wired cable that is designed specifically for the WellTell X device Figure 6 Wireless Host Wired to COM 2 of XFC 195 Step 4 Configuring COM 2 for the LevelMaster Application After completing the electrical wiring for the WellTell X to COM 2 on the flow c...

Страница 8: ...steps powering the unit and wiring the RS 485 to the LevelMaster sticks Step 5 WellTell IS Client Electrical Wiring The WellTell IS client can be mounted near or at the top of the storage tank It should be mounted in a Division 2 or non hazardous location however a short piece of cable can be run to the LevelMaster itself The WellTell IS client also has an onboard battery charger to maintain the c...

Страница 9: ...r Sticks to the IS Barrier The second part of the electrical installation for the WellTell IS is the wiring of the LevelMaster sticks to the IS barrier on the WellTell IS Figure 9 illustrates how this is accomplished Figure 9 Wiring LevelMaster Sticks to the IS Barrier ...

Страница 10: ...hannel etc Lesser used parameters i e Encryption Key Range Refresh etc are grayed out if Restricted Use is selected Normal setup does not require Restricted Use These lesser parameters can be accessed through Admin Admin is achieved by entering the password The factory password is 0000 As opposed to providing an in depth screen by screen explanation of the WWU the opening screen is presented to th...

Страница 11: ...t settings Figure 10 WWU Main Screen 7E PC Port tab Set the parameters as follows Parameter Field Value Port COM 1 Communication port of laptop PC Baud Rate 9600 Data Bits 7 or 8 bits based on user setup Parity Even Odd None based on user setup Stop Bits 1 ...

Страница 12: ...ing an in depth screen by screen explanation of the WWU please refer to Figure 10 to view the available tabs As with the previous section the following details each individual tab available to the user and the corresponding parameter fields and values that must be entered therein 8A System Config tab Set the parameters as shown in Figure 10 8B Radio Config tab Set the parameters as follows Paramet...

Страница 13: ... and configured as it would be without the WellTell products With the system up and running the WellTell X host display looks similar to Figure 11 Figure 11 WellTell X Host Display The antenna symbol is on The symbol is always active on the WellTell X or host server The is the system heart beat and blinks continuously The blink slows down whenever the radio is dead or not connected The F3 in the u...

Страница 14: ...evice Port or the radio More on this topic can be found in the WWU Help Files When the UP arrow is on the Microprocessor can snoop the Device Port If the UP arrow is not on the microprocessor can snoop the radio Snoop is only operational in Pass Through mode i e the Left and Right arrows are lit The DOWN arrow being on informs the user that the microprocessor is being connected in the Routing Matr...

Страница 15: ...ent b Ex 9600 b Baud rate displayed in Numeric section n Ex n 1 Network ID displayed in Numeric section ch Ex ch 2 Channel displayed in Numeric section b Ex b 12 3 Battery voltage displayed in Numeric section t Ex t 72 1 Temperature displayed in Numeric section I O and Barrier Clients Not Applicable to the Host Server c Ex c 0 Charger voltage L Ex L 5 Lithium cell voltage Barrier Clients Only Not ...

Страница 16: ...ABB Inc Totalflow Products 7051 Industrial Blvd Bartlesville Oklahoma 74006 Tel USA 800 442 3097 International 001 918 338 4880 ...

Отзывы: