Procedure
WBPEEUI210509A1
PR10 - 3
Power Disconnected from Single Power Supply Tray
The power supply trays can be removed from an operational
control system. This procedure assumes that the remaining
installed power supply tray is operational and that its status
light is on.
□
1. Open the front door to the cabinet.
□
2. Turn off the circuit breaker on the PEP to the line (LINE 1
or LINE 2) that powers the power supply tray to be removed.
□
3. Remove the power cord from the front of the power supply
tray.
□
4. Turn the two thumbscrews (Figure
PR10-1
) counterclock-
wise to release the power supply tray from the power chassis.
□
5. Slide the power supply tray out of the power chassis.