background image

 

I N S TA LL ATI O N  M A N UA L 

Stanilite®

Exit LED edgelit surface mount

Emergency, Nexus® LX, Nexus RF

Doc no. 29-00074_10

Thank you for choosing ABB product

Please read this document thoroughly before 
commencing installation and retain for future 
reference. Contact ABB customer service in 
Australia on 1800 60 20 20 if you need any 
assistance. The installation instructions were 
correct at the time of print. To reflect changes in 
technology and Australian standards; ABB 
reserves the right to amend the instructions 
without notice. Updated document can be found 
on the Stanilite website.

Safety warning

In Australia and New Zealand, only licensed 
electricians are permitted by law to work with 
240 volt electrical installations.
Do not attempt to install or connect this product 
unless you are a licensed electrician.
Turn off and isolate the electrical supply before 
connecting this fitting to the building wires.
Do not touch the terminals of the terminal block 
when the light fitting is energised.
The only user-serviceable part is the battery 
pack. LED light source is not user-serviceable.
Do not attempt to service other parts of the 
fitting as this will void the warranty.
As the installer, it is your responsibility to ensure 
compliance with all relevant building and safety 
codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to 

This document covers

What’s inside the box

Safety warning

Surface mount base 

assembly

Installation instructions

Diffuser assembly

Removal instructions

Surface mount base cover

Testing precautions

Pictograph insert pack

Troubleshooting guide

Installation manual

Warranty information

Important to note:

•  This product is designed for indoor use only.

Construction sites

Continuously switching off the mains power 
supply that is connected to emergency light 
fittings during the construction phase of an 
installation will cause these fittings to discharge 
and charge their batteries many times over a 
short period; this can shorten life of the battery. 
ABB does not recommend such practices and 
may not honour the warranty on batteries when 
they are subjected to such harsh operating 
conditions. Emergency light fittings are designed 
to be discharge tested once every 6 months as 
per AS/NZS 2293.2, subjecting the product to 
repeated discharge or charge cycles is regarded 
as an abuse of the fittings.

Troubleshooting guide

If you have installed and connected the fitting as per the instructions listed earlier and it does 
not function correctly, use the following table as a guide to fixing the problem. Look up the 
type of fault in the left column and check the possible causes from the right column.  

If the fitting still does not work after checking these possible causes, contact ABB customer 
service in Australia on 1800 60 20 20.


ABB Australia Pty Limited

For enquiries
ABB contact centre: 1800 60 20 20
E-mail: [email protected] 

www.stanilite.com.au

© Copyright 2020 ABB. All rights reserved. 

9

A

K

K

10

6

71

3A

9

5

72 - B - J

an 2

0

20

Testing precautions

Once the fitting is permanently connected to the 
mains supply, a commissioning discharge test as 
required in AS/NZS 2293.2 must be carried out. 
You will need to allow 24 hours for the battery to 
fully charge prior to conducting this test, 
presently (at the time of writing), the standard 
requires that fittings operate in emergency mode 
for a period not less than 2 hours for their 
commissioning test and for not less than 90 
minutes thereafter (it is required that 6 monthly 
discharge tests be carried out). You will need to 
keep the records for the commissioning test and 
enter them into the building emergency services 
logbook or via other recording methods as 
allowed by AS/NZS 2293.2.

the applicable standards for data and mains 
cabling installation procedures and 
requirements.

Nexus LX (data cable system)

The Nexus range of emergency light fittings are 
designed to be connected together into a special 
communication network over a level 4 (or higher) 
high speed, single twisted pair data cable. The 
Nexus user and technical guide describes all you 
need to know to successfully install a Nexus project. 
Ask for it from your superviser, from your employer 
or from your nearest ABB product supplier. The 
network cabling of the building must be installed 
as per the procedure detailed in the Nexus user and 
technical guide. No mains or mains carrying cables 
are to be connected to the data terminals or cables.

Nexus RF (wireless system)

The Nexus RF range of light fittings are designed to 
communicate via a proprietary RF network, however 
the electrical installation of the fittings is identical 
to that of a standard non-monitored fitting.

No. Fault

Possible causes

1

LED lamp and indicator LED not lit

AC supply not connected; 

or

AC supply turned off; 

or

Test switch damaged

2

LED lamp not lit but red indicator is lit

LED lamp damaged; 

or

LED lamp plug incorrectly inserted in the mother board

3

LED lamp not lit but indicator LED is flashing green

LED lamp damaged; 

or

LED lamp plug incorrectly inserted in the mother board

4

LED lamp is lit but red indicator LED not lit

LED damaged; 

or

Check battery connection

5

The LED lamp does not switch to emergency mode 
when the test button is pressed

Test switch damaged

6

Indicator LED is constant green

Test switch damaged; 

or

Self check fail - return to factory

7

Indicator LED not red after commissioning

Check battery connection and battery plug polarity

8

The LED lamp works momentarily on emergency 
when the test button is pressed or tested by 
command from the Nexus system

Battery not yet charged (allow up to 24 hours)

Отзывы: