background image

Active Neutral Earth

Quickfit 

mounting 

bracket

Insert here 

to remove

Terminal 

block

For ceiling mount; 

screw through 

holes labelled ‘A’
For wall mount; 

screw through 

holes labelled ‘B’ 

via slot ‘C’
To fit fitting to 

mounting bracket 

insert at 1 then 2

Cable entry 

holes

Figure 2: Quickfit insertion diagram and internal view

Figure 1: Quickfit terminal block connection

Terminal 

block

Quickfit 

mounting 

bracket

Cable 

entry 

hole

Insert 

here to 

remove

Figure 3: Quickfit vertical wall mounting

Vertical wall mounting
1. 

If mounting exit vertically on side wall, you 
must allow approximate 50mm free space 
above the ceiling bracket in order to slide the 
exit (step 2) into ceiling bracket.

2. 

The exit must only be installed as per figure 3, 
that is, with the terminal block at the top. This 
is to ensure that the exit is securely held and 
cannot inadvertently slide out of the bracket.

Installation instructions
1. 

Take the mounting bracket and whilst holding it into place against the ceiling or wall, use a pencil 
to mark the position of the screw holes (at A or B in figure 2) and cable entry position through the 
bracket onto the ceiling or wall as appropriate. Make sure to allow at least 50mm of free space to 
the right hand side of the final location of the fitting to allow for the sliding function of attaching 
the fitting to the mounting bracket. If need be, turn the bracket around and swap the diffuser with 
the back plate to permit room for inserting and removing the fitting from the mounting bracket. 
Orient the bracket in such a way as to make the LED and push button readily visible and accessible 
when the fitting is installed.

2. 

Remove the bracket to reveal the pencil marks and if the cabling is to be concealed, drill a 20mm 
hole for the cable entry prior to installing the bracket. Make sure the mounting screw locations are 
into solid material and strong enough to support the weight of the complete fitting, (approx 2kg: 
build-up, strengthen or support the mounting material if necessary) and attach the bracket. 
Because of the wide variety of building construction materials and the wide variety of screw 
fasteners appropriate to each type, mounting screws are not provided with the fitting. If 
appropriate and safe, drill and use your own fixing holes in the mounting bracket to suit the 
individual installation location and structural support needs of the fitting, taking care not to 
obstruct the fitting slide entry.

3. 

Run the cables in the ceiling or wall space as appropriate or surface mounted in conduit and 
through the cable hole into the bracket. Strip, connect and terminate the cables as indicated in 
figure 1. Ensure that the double insulation of the cable/s passes completely into the terminal block 
enclosure so that no single insulation is exposed when the cover plate is in place. The hole plug set 
includes a suitable bush to mechanically protect the cable as it passes though the opening in the 
mounting bracket. Likewise, the single insulation of the conductors should run right up to the 
metal edge of the terminals leaving no bare conductors outside of the terminals. Be careful with 
multi-strand conductors that all of the strands are twisted together before insertion into the 
terminal. Any stray strands that inadvertently come into contact with their neighbouring terminal 
of the metal frame of the fitting will cause undesirable results when the fitting is powered.

Removal instructions
1. 

Gently insert a small screwdriver into the slot 
(at ‘D’ in figure 2) on the front of the bracket 
towards the right hand end of the fitting, to 
ease the locking tab into the fitting and away 
from the bracket.

2. 

The fitting is then free to slide to the right 
along the bracket for about 50mm, at which 
time the slots line up and it can be lowered 
away from the bracket, allowing the two to 
separate.

3. 

The fitting will automatically switch into 
emergency mode because it has been 
removed from the power supply. It will stay on 

emergency until such time as the battery cut-
off threshold is reached or it is reconnected 
back onto the power supply, whichever 
happens first.

4. 

When the fitting is reconnected to the supply, 
it will need time to recharge its battery before 
it will be capable of a full length discharge 
again. The ability of the fitting to operate on 
emergency is determined by the age, charge 
level, operating temperature conditions and 
environmental circumstances of the battery in 
the fitting.

4. 

Attach the fitting to the mounting bracket by aligning the top left hand end of the fitting (the end 
without the protruding electrical connecting metal lugs) with the large cut-away slot towards the 
left hand end of the bracket. Slip the left hand end of the fitting up into the slot in the left hand 
end of the bracket (step 1 in figure 2) and hold the fitting horizontal to and parallel with the 
bracket. It should be approximately 50mm to the right of its final destination. Simply slide the 
fitting (step 2 in figure 2) 50mm to the left along and into the bracket to engage the connections 
and the locking tab. Once in place, the fitting cannot be removed from the bracket without the use 
of a tool (a small screwdriver) to push in the locking tab at ‘D’ in figure 2. Ensure the correct 
pictograph inserts have been attached to the diffuser assembly.

5. 

Once powered up, the normal AC LED light source will energise and remain lit until the power 
supply fails. The emergency function of the light fitting will only operate when the normal lighting 
power supply fails or when somebody presses the manual test button located on the front of the 
fitting. Red LED indicates that the power is connected and the battery is charging.

•  Maintained fittings are designed for 

permanent illumination: connect incoming 
unswitched active, neutral and earth to 
terminal marked USA, N and E respectively.

•  Connect DALI control wires/Nexus data cable 

to terminal and - respectively.

6. 

Check the operation of the fitting to ensure that the installation was successful. When powered 
up, allow a few minutes to give the battery a small charge, then press the manual test button 
located at the front face of the fitting. Hold the test button in for a few seconds and observe the 
operation of the LED light source switching from mains to the emergency mode. If the LED light 
source on emergency mode works momentarily, that’s okay. Try again in a few more minutes 
because if the battery was completely discharged, it may take a little time to charge up enough to 
operate even momentarily. After this time, press the test button again, and if the LED light source 
does not work at all, check the supply, the connections and the troubleshooting guide at the end of 
this document.

Important: If installing this product into an early version ceiling bracket, first remove the 2 hole 
blanking plugs on the front face of the bracket and replace with the short hole plugs provided with 
the product.

Important: 24 hours is required to allow the fitting battery to reach full capacity, ie: prior to a 
discharge test. As the installer, it is your responsibility to conduct the initial discharge testing of 
the installed fitting. Refer to AS/NZS 2293.