background image

Installation instructions

 

1. 

Insert a small flat head screwdriver into the locking slot on the front of the fitting (above LED and 

test switch, figure 1a), lift up the locking tab to unlock the bracket from the main fitting. The 

fitting is then free to slide out from the bracket. 

2. 

The economy exit LED slide connect can be installed either ceiling or wall mounted. Orient the 
bracket in such a way as to make the LED and push button readily visible and accessible when the 
fitting is installed. Use the bracket as a template to mark the mounting holes and cable access 
position.

•  For ceiling mounted; knock out the cable access hole. Hold the bracket against the ceiling, mark 4 

mounting holes and the cable access hole (figure 1b).

• 

For wall mounted; drill 2 holes (ø4 - ø5mm) at the “V” shape feature in the back of the bracket 
(figure 1c and 1d) and knock out the cable access (figure 2). Hold the bracket against the wall, mark 

2 mounting holes and the cable access hole.

3. 

Mount the bracket to the ceiling or wall using appropriate fixings (not supplied due to the wide 

variety of building construction materials).

4. 

Run the cables in the ceiling or wall space as appropriate and through the cable access hole into 
the bracket. Strip 9mm insulation length, connect and terminate the cables as indicated in figure 2. 
Ensure that the double insulation of the cable/s passes completely into the terminal block 
enclosure so that no single insulation is exposed when the cover is in place. Be careful with multi-
strand conductors that all of the strands are twisted together before insertion into the terminal. 
Any stray stands that inadvertently come into contact with their neighbouring terminal will cause 
undesirable results when the fitting is powered.

5. 

Economy exit LED slide connect is designed for permanent illumination; connect incoming 
unswitched active, neutral and earth to terminal marked A, N and E respectively. When connected, 
replace the terminal block cover so that it clicks and locks into place.

6. 

Attach the exit fitting to the bracket by aligning the sliding feature on both ends (figure 1a and 2). 

Once aligned, gently push the exit fitting into the bracket to engage the mains connections and 
locking tab. The economy exit LED slide connect is supplied standard with all options of 
pictograph inserts, ie: straight, left and right. Insert the appropriate pictograph onto the diffuser.

7. 

Once powered up, the normal AC LED light source will energise and remain lit until the power 
supply fails. The emergency function of the light fitting will only operate when the normal lighting 
power supply fails or when somebody presses the manual test button located on the front of the 
fitting. Red LED indicates that the power is connected and the battery is charging.

8. 

Check the operation of the fitting to ensure that the installation was successful. When powered 
up, allow a few minutes to give the battery a small charge, then press the manual test button 
located at the front face of the fitting. Hold the test button in for a few seconds and observe the 
operation of the LED light source switching from mains to emergency mode. If the LED light source 
on emergency mode works momentarily, that’s okay. Try again in a few more minutes because if 
the battery was completely discharged, it may take a little time to charge up enough to operate 
even momentarily. After this time, press the test button again and if the LED light source does not 
work at all, check the supply, the connections and the troubleshooting guide at the end of this 
document.

Cable entry knock out instructions

Ceiling mount

•  Use screwdriver to punch through the plastic 

(figure 3a).

• 

Use wire cutter to cut the rib (figure 3b).

Wall mount

•  Use wire cutter to cut around the edges 

(figure 4a).

• 

Use pliers to remove the plastic (figure 4b).

Removal instructions
1. 

Insert a small flat head screwdriver into the 
locking slot on the front of the fitting (above 

LED and test switch, figure 1a).

2. 

Lift up the tab to unlock the bracket from the 
main fitting. The fitting is then free to slide 
out from the bracket and it can be lowered 
away from the bracket, allowing the 2 to 
separate.

3. 

The fitting will automatically switch into 
emergency mode because it has been 
removed from the power supply. It will stay on 

emergency until such time as the battery cut-
off threshold is reached or it is reconnected 
back onto the power supply, whichever 
happens first.

4. 

When the fitting is reconnected to the supply, 
it will need time to recharge its battery before 
it will be capable of a full length discharge 
again. The ability of the fitting to operate on 
emergency is determined by the age, charge 
level, operation temperature conditions and 
environmental circumstances of the battery 
in the fitting. 

Important: 24 hours is required to allow the fitting battery to reach full capacity, ie: prior to a 
discharge test. As the installer, it is your responsibility to conduct the initial discharge testing of 
the installed fitting. Refer to AS/NZS 2293.

Figure 1: Mounting holes position for wall or ceiling mount

Insert flat head screwdriver and 

push up to unlock the locking tab

1a

Mounting holes

Cable access to be removed 

for ceiling mounting

Locking tab

1b

220

50

Figure 2: Terminal block connection and internal view

Terminal 

block 

cover

Cable access to be 

removed for wall 

mounting

Sliding 

feature

2

1c

Drill to suit wall 

mounting

1d

220

Figure: 3a

Figure: 3b

Figure: 4a

Figure: 4b

Отзывы: