ABB SRW Скачать руководство пользователя страница 2

I.L. 41-252A

2

for tripping or alarm purpose. These relays will
be sealed in by a reed relay contact if a trip
current is detected.

(5)

Reed relay and reset switch — The reed relay

is for monitoring and indication of the actual
trip current flow. The trip current should be
between 0.5 and 30 amperes. Once the trip
current is detected, the reed relay seals in the
trip relays and turns on the trip indicator which
is a magnetic flip-flop disc indicator on the
SRW board. The indicator is reset from the
outside of the case by a push rod located at
the bottom of the cover. With the relay being
energized, the rod touches a push-button
switch and resets the target.

2.2.

SRW Module

The SRW module, located at the top of the relay,
contains two LEDs, one magnetic flip-flop indicator,
one thumbwheel switch, one 6PST DIP switch, sev-
eral integrated circuits and associated components.

(1)

Indicators

(a) A yellow LED is for the dc power-on condi-

tion.

(b) A red LED indicates that the magnitude of

the reverse power is above the pickup set-
ting.

(c) A magnetic flip target shows that the actual

trip current is detected.

(2)

Pickup setting switch — A single pole 10 posi-

tion (SP10T) thumbwheel switch is used. Each
number (or position) represents a reverse
power pickup setting between 1 mA and 40
mA.

(3)

Time delay selection — A DIP package con-

taining six SPST switches is used. Each SPST
switch indicates its own delay time. The total
delay time is the summation of the selected
individual times. The timer can be set in steps
of .05 sec. for .2 to 2, .5 sec. for 2 to 21.5 sec
and 1.0 sec for 2 to 63 sec.

(4)

All integrated circuits and electronic compo-

nents are used for detecting the power direc-
tion, level, undervoltage condition and trip
logic. If the input voltage is above 30% of rat-
ing and the reverse power level is above the

pickup value persisting longer than the
selected delay time, the logic will energize the
trip relays and close their output contacts.

2.3.

Transformer In-rush Module

The In-rush module is located on top of the SRW
module and electrically connected by two bottom
entry connectors to the SRW module. This module
contains five integrated circuits and several discrete
components. A blue link L1 is used to select the
power supply voltage for this module. Positions are
available for 48, 125 or 250 Vdc with the 125 volt set-
ting being the relay shipping setting. The theory upon
which the SRW relay function is based assumes a
sinusoidal waveform which is true for a reverse
power condition. Conditions can occur however,
when the waveform is not a sinusoid, such as an ini-
tial energization of a transformer with little or no load
connected. When a transformer is first energized, a
transient magnetizing or exciting in-rush is not a sine-
wave and may last for several minutes before finally
damping out. The actual time depends on several
factors such as size and location of the transformer,
resistance of the power system from the generator to
the transformer, the saturation density of the trans-
former, residual flux level in the bank and how the
bank is energized. The SRW, due to its high sensitiv-
ity, may false trip after its timer times out under these
types of conditions. The In-rush module will prevent
these types of false trips.

3.

THEORY OF OPERATION

The SRW relay is a single phase directional relay
used to protect ac generators from motoring. It
senses the power flow into the generator. If this
power flow persists for a predetermined time, the
generator may be tripped. The relay must sense and
perform the computation of

 to

determine a trip, where

I

 is a single phase current

(e.g.,

I

a

) and

θ

is the angle by which this current

leads the voltage (e.g., Vac). The maximum sensitiv-
ity angle occurs when the angle

θ

 equals 30 degrees.

The sensitivity of the reverse current is 1 milliampere,
and the continuous current capability is 10 amperes.

This relay can be easily modified and adjusted for
any desired maximum sensitivity angle between 0
and 90 degrees.

A block diagram of the SRW relay is shown in

Figure

I

θ

30

°

(

)

cos

×

Содержание SRW

Страница 1: ...s from 1 mA to 40 mA at the maxi mum sensitivity angle 2 CONSTRUCTION The SRW relay consists of three printed circuit mod ules and a front panel packaged in a FT 11 case For detailed information on the flexitest case refer to I L 41 076 The photograph in Figure 1 shows the SRW relay in its case 2 1 Interface Module The interface module mounted at the bottom of the relay contains a voltage transfor...

Страница 2: ... their output contacts 2 3 Transformer In rush Module The In rush module is located on top of the SRW module and electrically connected by two bottom entry connectors to the SRW module This module contains five integrated circuits and several discrete components A blue link L1 is used to select the power supply voltage for this module Positions are available for 48 125 or 250 Vdc with the 125 volt...

Страница 3: ... φ equals 0 Since signal C leads Vac by 30 the maximum sensitivity occurs when Ia leads Vac by 30 Assume that Ia and signal E are in phase It can be compensated by adjusting the phase shifter between points A and B for any phase shift caused by possible component imperfections To produce a trip the dc component cos φ must be positive i e the angle φ is between 90 and 90 To stay in restraint cos φ ...

Страница 4: ...ected as a differential amplifier whose output voltage is proportional to the input current Ia from 1 mA to 5 amps The phase angle relationship remains constant between 1 mA and 50 amperes The multiplier circuit contains IC7 IC4 A R61 R62 R63 and R64 The gain of IC7 is 1 or 1 for the open or closed contact in switch IC4 A respectively The output waveforms of the multiplier are shown in Fig ure 10 ...

Страница 5: ... The maximum temperature outside the relay case should not exceed 55 C for normal operation see CHARACTERISTICS for temperature range specification Mount the relay vertically by means of the four mounting holes on the flanges for semi flush mount ing For projection mounting install the special pro jections mounting hardware provided in mounting material kits when required Either the installed pro ...

Страница 6: ...or 70 Vac to term 6 7 Adjust the phase shifter to read I leading V by 30 deg on the phase angle meter 3 Connect CH 1 of the dual trace scope to TP3 and CH 2 to TP4 Two waveforms should be in phase 4 Connect a digital voltmeter to TP1 and its common to TP5 The reading should be higher than 13 volts 5 Adjust the phase shifter until the meter reads zero volts at TP1 the phase angle meter should be 30...

Страница 7: ...y and all settings and times of operation should be checked at least once every year or at such other intervals as may be indicated by experience to be suitable to the particular application 8 1 Calibration The proper adjustments of the trimpots P1 P2 P3 and P4 have been calibrated by the factory and should not be disturbed by the customer unless the relay is out of calibration shown in the Accept...

Страница 8: ...lay for 10 seconds by either opening DIP switch 1 10 sec or open ing switches 2 5 sec 3 3 sec and 4 2 sec c Turn on ac and dc voltages Set the input current at 1 ampere and adjust the phase shifter for current leading voltage by 30 deg d Turn on SW 1 suddenly The digital timer should give a reading of 10 seconds 5 If the reading is too high remove capacitor C2 and or C4 from the PC board e Check t...

Страница 9: ...Interface Module 1500B49 7 Component Location In rush Module 1499B41 8 External Schematic of the Type SRW Relay for Reverse Power Protection 1495B45 9 External Schematic of the SRW Relay to Prevent Reverse Magnetization When Utility Tie is Removed From the Local System 1495B46 10 Multiplier Waveforms 9645A93 11 Test Connection for the SRW Relay 1495B54 12 Outline and Drilling Plan for the SRW Rela...

Страница 10: ......

Страница 11: ...I L 41 252A 11 Figure 2 Simplified Terminal Connection Drawing 9645A75 Sub 3 Denotes Change ...

Страница 12: ...I L 41 252A 12 Figure 3 SRW Block Diagram Sub 2 1495B44 Denotes Change ...

Страница 13: ...I L 41 252A 13 Figure 4 Internal Schematic SRW Relay Sheet 1 of 2 Sub 4 1355D79 Denotes Change ...

Страница 14: ...I L 41 252A 14 Figure 4a Internal Schematic SRW Relay Sheet 2 of 2 Sub 4 1355D79 Denotes Change ...

Страница 15: ...I L 41 252A 15 Figure 5 Component Location SRW Module Sub 2 1500B50 Denotes Change ...

Страница 16: ...I L 41 252A 16 Figure 6 Component Location Interface Module Sub 4 1500B49 Denotes Change ...

Страница 17: ...I L 41 252A 17 Figure 7 Component Location In Rush Module Sub 3 1499B41 Denotes Change ...

Страница 18: ...I L 41 252A 18 Figure 8 External Schematic of the Type SRW Relay for Reverse Power Protection Sub 2 1495B45 Denotes Change ...

Страница 19: ...I L 41 252A 19 Figure 9 External Schematic of the SRW Relay to Prevent Reverse Magnetization When Utility Tie is Removed from the Local System Sub 3 1495B46 Denotes Change ...

Страница 20: ...I L 41 252A 20 Figure 10 Multiplier Waveforms Sub 1 9645A93 ...

Страница 21: ...I L 41 252A 21 Figure 11 Test Connection for the SRW Relay Sub 2 1495B54 ...

Страница 22: ......

Отзывы: