24
CHART CONTROL
CONFIGURATION
CHART SPEED 1
mm/hr
CHART SPEED 1 SOURCE
PAPER OUT ALARM
I/P FAILURE
DIGITAL I/P
CHART SPEED
POWER FAILURE
PROCESS ALARM
NONE
CHART SPEED 2
mm/hr
CHART SPEED 2 SOURCE
CHART SPEED 3
mm/hr
CHART SPEED 3 SOURCE
…3
CONFIGURATION
3.4
Chart
3.4.1
Chart Control Configuration Page
Information.
•
Set up to 3 independent chart speeds – selectable from operating level or by digital signal.
•
Enable/disable printing of text (except alarms).
•
NO AUTO PRINT
facility – allows an unbroken trace at higher chart speeds (> 120mm/h), with printing of time, scales,
etc. at the start and end of a batch.
•
Enable/disable alarm printing.
•
Text can be selected to be printed fast or slow.
•
Auto pen-drop – automatically returns the pen capsule to an operating state after a 5 minute delay to ensure recording is
not inadvertently left disabled.
•
Easy View feature – allows quick access of latest printed information.
•
Time Line Advance – allows the chart to be advanced to the required time line before commencing recording.
Set Chart Speed 1
Select a chart speed between 0 and 1500mm/hr.
Chart Speed 1 Source
Select the source required to initiate a change to chart speed 1:
PAPER OUT ALARM
– End of chart reached
I/P FAILURE
– Failure of analog input (A1 to A6)
DIGITAL I/P
– Active digital input (DA1)
CHART SPEED
– Selection of chart speed (1 to 3)
POWER FAILURE
– After power failure
PROCESS ALARM
– Pre-defined process alarm (A to M, excluding I)
NONE
– No automatic action
Set Chart Speed 2
Select a chart speed between 0 and 1500mm/hr.
Chart Speed 2 Source
Select a chart speed source as for chart speed 1 above.
Set Chart Speed 2
Select a chart speed between 0 and 1500mm/hr.
Chart Speed 3 Source
Select a chart speed source as for chart speed 1 above.
Continued on next page.
Information. A chart speed of 120mm/hr is required when digital input DA1 is active. At all other times set chart speed
to 20mm/hr.
•
Set chart speed 1 to 20mm/hr
•
Set chart speed 1 source to
CHART SPEED 2
•
Set chart speed 2 to 120mm/hr
•
Set chart speed 2 source to
DA1
Select chart speed 1 and start recording. When DA1 becomes active the chart speed changes to 120mm/hr.
When DA1 becomes inactive the chart speed returns to 20mm/hr.