3
2.4
Termination Resistors – Fig. 2.2
Under normal operating conditions the slave termination resistors are linked out. For long transmission lines, termination resistors
are required on the last slave in the chain and the host computer/computer terminal – see Fig. 2.2A. The slaves termination
resistors are linked-in using plug-in link (LK1) on the serial module – see Fig. 2.2B.
2.5
RS485/422 Standard
The RS485 standard quotes connection of thirty-two slaves maximum, to any single driver (computer terminal or host computer);
the RS422 standard quotes connection of up to ten slaves. However, these numbers can be increased if the driver’s serial port permits.
2
ELECTRICAL INSTALLATION…
Position link
Termination
Resistors
Linked-out
Termination
Resistors
Linked-in
Identify Link
4
4
1
1
LK1
LK1
Serial Module
1
4
LK1
Internal Termination Resistors
Computer Terminal
or Host Computer
Advanced Process Recorder Slaves
Remove chassis
from case
1
2
3
Fig. 2.2 Slave Termination Resistors
Note. For long transmission lines, the internal termination resistors on the last slave in the chain must be linked-in.
A – Schematic Diagram
B – Termination Link Positions