13
Example 4.
Biased differential relay SPAD 330 C used for
the winding short-circuit and interturn fault
protection of a Dyn11 connected power
transformer, when the current transformers
have “inside” earthings, i.e. the current
transformers have the basic connection type I.
Switch
SG1
1
1
2
0
3
0
4
1
5
0
6
0
∑
= 9
Setting of the matching of the power transformer
vector group:
SPAD 330 CSPAD 330 C
P1
S2
P2
S1
P2
P1
S2
S1
L1
L2
L3
SPAD 330 C
B