Power supply connections

Transmitter power supply module

One transmitter power supply module can be fitted in position D 
to provide a nominal 24 V supply capable of driving two, 2-wire 
transmitters.

Fig. 8 Single analog / digital input connections

Fig. 9 Dual analog / digital input connections

IMPORTANT (NOTE)

Tighten all analog / digital input 

terminal screws to a torque of 0.5 Nm (4.5 lbf.in).

1    2    3     4

1   2    3    4

1   2    3    4

1   2    3    4

1   2    3    4

1   2    3    4

*In the powered-down condition the current input is open circuit. 
In order to maintain a current loop when the recorder is powered 
down, fit a zener diode (BZX79 – B/C2V4) to the input as shown.

Voltage

Current

Thermocouple

3-lead RTD

4-lead RTD

Digital input

(volt-free or 24 V

)

Each lead must be of equal

resistance and less than 10 

Logic state inactive

Logic state active

Thir

d lead

Whit

e

Red

Red

1   2    3    4

1   2    3    4

1   2    3    4

1   2    3    4

*In the powered-down condition the current 
input is open circuit. In order to maintain a 
current loop when the recorder is powered 
down, fit a zener diode (BZX79 – B/C2V4) to 
the input as shown.

Voltage

Current

Thermocouple

Input 1 Input 2

Digital input

(volt-free or 24 V

)

Logic state inactive

Logic state active

Input 1 Input 2

Input 1 Input 2

Input 1 Input 2

Fig. 10 Power supply connections

IMPORTANT (NOTE)

Tighten power supply terminal 

screws to a torque of 0.8 Nm (7 lbf.in).

Fig. 11 Power supply connections

A – AC supply

Warning.

Use fuse rating 315 mA (max.) type T

100 V min. to 240 V max, 
50 / 60 Hz

B – DC supply

Fuse

305 mA, type T

Line

Neutral

Fuse

1.5 A, type T

10 V min. to 36 V max, DC

Warning.

Use fuse rating 1.5 A (max.) type T

1   2    3    4

Tx

2-wire transmitter power supply 
(24V DC, 22mA max.)

Analog input

Содержание SM500F

Страница 1: ...tions AC and DC min max values and fuse requirements 4 Navigation navigating the user interface quickly and effectively 5 Menus overview menu familiarization 6 Basic setup steps required for first tim...

Страница 2: ...RNING Bodily injury Installation and maintenance of this product must only be conducted by personnel authorized to work on electrical installations and in accordance with relevant local regulations WA...

Страница 3: ...d Environmental Operating temperature range 10 to 50 C 14 to 122 F Operating humidity range 5 to 95 RH non condensing Storage temperature range 20 to 70 C 4 to 174 F Enclosure sealing IP66 and NEMA4X...

Страница 4: ...If this is not possible particularly in applications where mobile communications equipment is expected to be used screened cables within flexible earthed metal conduit must be used Fig 1 Siting C Avoi...

Страница 5: ...left and right hand mounting brackets A into the recesses on the rear of the recorder as shown and secure with bracket securing screws B Ensure the plastic washers remain in the positions fitted 2 Ma...

Страница 6: ...nting bracket using two M6 x 8 mm long hexagon head screws B and two spring lock washers C 3 Position the pipe mounting bracket into the recesses on the rear of the recorder as shown and secure with t...

Страница 7: ...s for example terminals Terminals for external circuits are for use only with equipment with no accessible live parts If the recorder is used in a manner not specified by the Company the protection pr...

Страница 8: ...is fitted 4 Connect Ethernet cable D ensuring that if optional input modules are fitted in positions B and C the cable is routed between their terminal blocks as shown 5 Connect cable screens only to...

Страница 9: ...mV V digital input Current R RTD 3 RTD 4 Current I P 1 I P 2 Dual relay Relay 1 Relay 2 Relay 1 Relay 2 NO NC LK2 Relay NO NC LK1 C NO NC 10 to 36 V DC or 100 to 240 V AC In the powered down conditio...

Страница 10: ...ead must be of equal resistance and less than 10 Logic state inactive Logic state active Third lead White Red Red 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 In the powered down condition the current input is ope...

Страница 11: ...ss group or Left key scrolls left C Up Down keys highlights menu items and scrolls through previously recorded data D View key selects a different process view or log or Right key scrolls right E Ente...

Страница 12: ...ighlight Configuration in the operator menu 2 Press and highlight the operator to log on as 3 Press and enter the operator password if configured 4 Select the configuration entry mode a Edit Current C...

Страница 13: ...Menu enables Indicator Indicator Totalizer statistics Bar graph display Alarm Trip Points Menu enables Archive Archive file format Archive file enables Wrap Batch If option enabled Enable Batch Recor...

Страница 14: ...nections Allowed Modbus TCP Port Reverse IEEE data Implementation Client Master Connections Allowed Modbus TCP Port Poll Rate ms Poll fail limit Response Timeout ms Comms analog I P Comms analog I P P...

Страница 15: ...and press the key to display the group s Recording tab 2 Use the keys to highlight the edit button next to each field and press the key to configure each parameter as required 3 Use the key to select...

Страница 16: ...d icons Archiving icons Status icons Alarm event icons IMPORTANT NOTE The recorder detects the type of module fitted in each position automatically SD card slot Display type Color Monochrome External...

Страница 17: ...Power failed Power restored Batch total Maximum value Minimum value Average value Daylight saving start end changed Power failed Power restored Calibration change Configuration change File deleted Ar...

Страница 18: ...18 CI SM500F EN Rev A Notes...

Страница 19: ...Sales Service Software CI SM500F EN Rev A 19...

Страница 20: ...l rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilization of its contents in whole or in parts is forbidden wi...

Отзывы: