2600T Series Pressure transmitters 266 models |
SOI/266-XC 11
The easy set-up procedure is made possible thanks to the intuitive
HMI, connected on the transmitter communication board.
To navigate the 266 HMI please follow the various indications that
will appear on the bottom of the display.
To facilitate commissioning the 266 HMI has the capability to run
a sequence of predefined setup steps with the main configuration
settings.
When you start the Easy Setup you must continue up to the end
to exit.
To start the Easy Setup:
Navigate the Digital LCD Integral Display menu, push the botton
on the right under the LCD display.
Define the Language
If the desired language is different from the indicated language
select
Edit
then scroll the desired language (see the following
table) with the up and down keys and confirm with
OK
. Select
Next
to continue.
English
German
Italian
Insert Tag
If the Tag number of the instrument is different from the value set
in the factory, use this part of the easy set-up menu to change it.
Define the PV Unit
If the desired Process Variable Unit is different from the indicated,
select
Edit
then scroll the desired unit (see the following table) with
the up and down keys and confirm with
OK
. Select
Next
to continue.
mbar
millibar
mmH2O°C
millimeter of water at 4 degrees Celsius
g/cm2
grams per square centimeter
inH2O°F
inches of water at 68 degrees Fahrenheit (20°C)
Kg/cm2
kilo grams per square centimeter
inHg°C
inches of mercury at 0 degrees Celsius
Pa
pascal
ftH2O°F
feet of water at 68 degrees Fahrenheit (20°C)
kPa
kilopascal
mmH2O°F
millimeter of water at 68 degrees Fahrenheit (20°C)
torr
torr
mmHg°C
millimeter of mercury at 0 degrees Celsius
atm
atmosphere
psi
pounds per square inch
MPa
Megapascal
bar
bars
inH2O°C
inches of water at 4 degrees Celsius
Define the PV Lower Range Value (LRV)
If the desired LRV is different from the indicated select
Edit
, scroll
the desired value for the digit in reverse color with the up and down
keys and confirm with
Next
.
Repeat the operation for the seven
digits and confirm with
OK
.
Select
Next
to continue
Define the PV Upper Range Value (URV)
If the desired URV is different from the indicated select
Edit
,
scroll
the desired value for the digit in reverse color with the up and down
keys and confirm with
Next
.
Repeat the operation for the seven
digits and confirm with
OK
.
Select
Next
to continue.
Define the Linearization Type
If the desired Linearization Type is different from the indicated
select
Edit
then scroll the desired Linearization Type (see the
following table) with the up and down keys and confirm with
OK
.
Select
Next
to continue.
Linear
Output = x
Square Root
Output = x
1/2
3/2
Output = x
3/2
5/2
Output = x
5/2
22 Points Table
Cylindric Spheric
Bidirectional Flow
Define the Low Flow Cut Off
If the desired Low Flow Cut Off for a Flow Transfer Function is
different from the indicated select
Edit
,
scroll the desired value for
the digit in reverse colour with the up and down keys and confirm
with
Next
.
Repeat the operation for the five digits and confirm with
OK
.
Select
Next
to continue.
Note
The minimum and maximum allowed values are indicated on
the display.
Define the Damping
If the desired Damping is different from the indicated value change
it with the up and down keys and confirm with
OK
.
Set PV to Zero
In case a Zero Scaling is required apply the pressure for the Zero
and select
OK
. Wait for the auto-set end (the bargraph will indicate
the working progress). Select
Next
to continue.
Define Hmi Line 1 View
By using this parameter you can chose what to see on the first
line of the Human Machine Interface. To change the value to be
shown, select
Edit
, scroll the desired value for the digit in reverse
color with the up and down keys and confirm with
Next
.
EASY SET-UP
Define the SQRT Linear Point
If the desired SQRT Linear Point is different from the indicated select
Edit
,
scroll the desired value for the digit in reverse colour with the
up and down keys and confirm with
Next
.
Repeat the operation
for the five digits and confirm with
OK
.
Select
Next
to continue.
Note
In case of PA or FF pressure transmitters, please consider as
mandatory the following steps.
Define the OUT Unit
If the desired Outup Unit is different from the indicated, select
Edit
then scroll the desired unit (all allowed Eng. Units) with the
up and down keys and confirm with
OK
. Select
Next
to continue.
Define the OUT Lower Range Value (LRV)
If the desired LRV is different from the indicated select
Edit
, scroll
the desired value for the digit in reverse color with the up and down
keys and confirm with
Next
.
Repeat the operation for the seven
digits and confirm with
OK
.
Select
Next
to continue
Define the OUT Upper Range Value (URV)
If the desired URV is different from the indicated select
Edit
,
scroll
the desired value for the digit in reverse color with the up and down
keys and confirm with
Next
.
Repeat the operation for the seven
digits and confirm with
OK
.
Select
Next
to continue.