ScreenMaster RVG200
Paperless recorder
7 Configuration
102
OI/RVG200-EN
7.9.5 Totalizer configuration
Note.
The totalizer tabs are displayed only if the Totalizer option is enabled.
Current totalizer values are displayed in the Indicator view – see Section 4.5.2, page 31
(Operation) and Section 7.8.3, page 84 (Configuration), respectively.
For analog sources, the total value of a signal is calculated by counting pulses produced at a rate
proportional to the input. For digital sources, off / on transitions are counted to produce a batch
total.
Totalizer A (B)
Setup
Mode
Select the totalizer operation mode:
Off
Standard (9 digits)
Standard (7 digits)
F
0
Timer
(digital totalizers only).
Direction
Note.
Displayed only if
Mode
is set to
Standard (9 digits)
,
Standard
(7 digits)
or
Timer
(digital totalizers only).
When
Direction
is set to
Up
, the totalizer counts up from the
Preset count
value to the
Predetermined count
value – see page 104.
Wrap enable
If
Wrap enable
is set to
On
, the total is reset automatically to the
Preset
count
value once the
Predetermined count
value is reached.
If
Wrap enable
is set to
Off
, the count stops when the
Predetermined count
value is reached.
Note.
A wrap pulse, with a duration of 2 seconds, occurs if the total
reaches the
Predetermined count
value and
Wrap enable
is set to
On
. If
Wrap
enable
is set to
Off
, the wrap pulse becomes active when the
Predetermined count
value is reached and remains active until the totalizer
is reset. The pulse can be assigned to a relay, digital output or digital
counter.