5. INSTALLATION
NOTE
The floor must be well leveled and the unit must be
fixed by means of anchor bolts in accordance with
the dimensional drawing for the number of modules
or units as appropriate.
The tolerance of the evenness is maximum 1 mm per meter.
Unit
A
B
C
1-way
298
337
371
2-way
623
662
696
3-way
948
987
1021
4-way
1273
1312
1346
5-way
1598
1637
1671
5.1 STANDARD 3-WAY SWITCHGEAR
NOTE
The tools required for installation and maintenance
of the switchgear are specified in the tool list in
chapter 20.6.