38
Code
Factory
Value and function
setting
V201
2
Setting of the data transfer rate
0 = 9600 bits/s, synch in
1 = 9600 bits/s, synch out
2 = 9600 bits/s
3 = 4800 bits/s
4 = 2400 bits/s
5 = 1200 bits/s
6 = 300 bits/s
I1
-
State of interlocking line 1
0 = not active state
1 = active state
I2
-
State of interlocking line 2
I3
-
State of interlocking line 3
I4
-
State of interlocking line 4
I5
-
State of interlocking line 5
I6
-
State of interlocking line 6
I7
-
State of interlocking line 7
I8
-
State of interlocking line 8
O1
-
Sate of output relay 1
0 = not active state
1 = active state
O2
-
Sate of output relay 2
C
0
Status information of module
0 = when read normal state, when written resets the status register
1 = CPU reset has occurred
2 = overflow of the event register has occurred
3 = 1 + 2
F
SACO
Type designation of module
16D2B
T
-
Time setting
0.000...59.999 = time in seconds and milliseconds
L
-
Event sequence register
Time, channel and event code
B
-
Repeated read out of event register
Time, channel and event code
A
-
Active alarms
Channel number and event code
Channel related parameters (alarm channels 1...16)
S1
0.02
Channel input delay
0.005...160.0 = reset delay
0.005 s steps
S2
0.02
Channel reset delay
0.005...160.0 = reset delay
0.005 s steps