![background image](http://html1.mh-extra.com/html/abb/sace-pr111/sace-pr111_manual_3438580012.webp)
ABB SACE
SACE PR010/T
RH0029002
L2551
11/67
67
WARNING
Connect the test wire provided (between the SACE PR010/T and the SACE
PR212/MP) the right way round (see drawing in par. 9).
Example of an automatic test application on the PR212/MP release
NOTE:
the data indicating the type of CB and protection and the current rating of
the CTs are automatically identified by the PR010/T test unit.
In this example, all the protection functions implemented by the SACE PR212/MP release are
tested automatically:
1. Set the PR212/MP in electronic set mode.
(ELT)
2. From the main menu select 1.
(Operation mode)
3. Select the PR212MP unit with x.
(PR212/MP)
4. Select the type of activity with 1
(Test)
5. Select the type of test with 1
(Protections)
6. Select the test mode with 1
(Automatic)
7. Pressing ENTER enables a simulation of the failure for each protection func-
tion.