Section 3 Technical Data and Performance
Capacity and Performance
3BSE015969-600 A
121
Capacity and Performance
Advant Fieldbus 100 Load
The bus load is calculated with different figures according to the bus length:
•
for bus length max 2000 m (2200 yards), use
•
for bus length max 8500 m (9300 yards), use
•
for bus length max 15000 m (16400 yards), use
.
To calculate the bus load in percent (AF100%load), at the required Cycle Time, the
CI810/CI820 (FCI) loading per station and the I/O Module Type quantity times the
per cent loading.
For bus load calculation, use the formula:
AF100
%load
= CI810/CI820
load
+ S800 I/O Module 1
load
+ S800 I/O Module n
load
+......
Calculation of load for AF100 with a length of max 2,000 m (2,200 yards)
Due to the organization of the Advant Fieldbus 100 scans, some constraints are
imposed on the transmissions. To guarantee message transfer etc., at least 30% of
the fieldbus load is reserved. The remaining load (up to 70%) can be used for S800
I/O station loading and other station loading.
Below is an example for an I/O station with one CI810 FCI, 2 AI810s,
two AO810/AO810V2s, four DI810s and four DO810s using 128ms cycle time for
AI and AO modules and 64ms for DI and DO modules:
AF100
%load
= 0.033% + (2 x 0.197%
AI810
) + (2 x 0.221%
AO810/AO810V2
)
+ (4 x 0.138%
DI810
) + (4 x 0.146%
DO810
) = 2.005% Load
The calculated load of Advant Fieldbus 100 must be equal to or less than 70%.
Содержание S800
Страница 1: ...Power and productivity for a better world S800 I O Product Guide ...
Страница 2: ......
Страница 3: ...S800 I O Product Guide ...
Страница 8: ...Table of Contents 8 3BSE015969 600 A ...
Страница 14: ...New in this Release About This Product Guide 14 3BSE015969 600 A ...
Страница 16: ...16 3BSE015969 600 A Safety Summary ...
Страница 78: ...ModuleBus Section 2 Product Description 78 3BSE015969 600 A Figure 30 TB820 TB820V2 ModuleBus Modem ...
Страница 88: ...ModuleBus Section 2 Product Description 88 3BSE015969 600 A Figure 37 Module Outlet Module TB845 ...
Страница 89: ...Section 2 Product Description ModuleBus 3BSE015969 600 A 89 Figure 38 ModuleBus Inlet Module TB846 ...
Страница 93: ...Figure 40 Power Supply Module SD831 Section 2 Product Description Power Supplies 3BSE015969 600 A 93 ...
Страница 94: ...Figure 41 Power Supply Module SD832 Power Supplies Section 2 Product Description 94 3BSE015969 600 A ...
Страница 95: ...Figure 42 Power Supply Module SD833 Section 2 Product Description Power Supplies 3BSE015969 600 A 95 ...
Страница 96: ...Figure 43 Power Supply Module SD834 Power Supplies Section 2 Product Description 96 3BSE015969 600 A ...
Страница 97: ...Section 2 Product Description Power Supplies 3BSE015969 600 A 97 Figure 44 Voting Unit SS823 ...
Страница 98: ...Power Supplies Section 2 Product Description 98 3BSE015969 600 A Figure 45 Voting Unit SS832 ...
Страница 172: ...Certifications Section 3 Technical Data and Performance 172 3BSE015969 600 A ...
Страница 174: ...Product and Price List Structure Section 4 Ordering 174 3BSE015969 600 A ...
Страница 178: ...Appendix A Hardware Units for Essential Automation 178 3BSE020924 600 A ...
Страница 182: ...Index 182 3BSE015969 600 A Index 182 3BSE015969 600 A ...
Страница 184: ...Revision History 184 3BSE015969 600 A ...
Страница 185: ......