30
F-9
Phase error : closest value is 180°.
he controller could not find
a known configuration
Check connections,
capacitors and fuses
F-10
Phase error : closest value is 210°.
The controller could not find
a known configuration
Check connections,
capacitors and fuses
F-11
Phase error : closest value is 240°.
The controller could not find
a known configuration
Check connections,
capacitors and fuses
F-12
Phase error : closest value is 270°.
The controller could not find
a known configuration
Check connections,
capacitors and fuses
F-13
Phase error : closest value is 300°.
The controller could not find
a known configuration
Check connections,
capacitors and fuses
F-14
Phase error : closest value is 330°.
The controller could not find
a known configuration
Check connections,
capacitors and fuses
F-15
C/k not found after 10 trials.
The load is varying too quicly
Re-start the Autoset procedure under
more stable conditions.
F-16
C/k too small ( < 0.05).
Step size too small or CT ratio too big.
Adapt the step size or the CT ratio.
F-17
C/k too high ( > 1.00).
Step size too big or CT ratio too small
Adapt the step size or the CT ratio.
Message
Description
Recommended action