Installation
42/68-285-EN
RSD10 ... 200 (Contrac)
13
Pos: 8.9 /Überschriften/1.1.1/1-spaltig/RSD50 / RSD100 / RSD200 @ 18\mod_1203677154375_0.doc @ 164616
3.2.2 RSD50 / RSD100 / RSD200
Pos: 8.10 /Montage/Aktorik/Linearantriebe/Allgemein/Einbaulage Zeich. RSD_RSDE 50/100/200 @ 18\mod_1203674845156_3101.doc @ 164287
Fig. 4
1
Inspection plug
2
Venting plug
Pos: 8.11 /Montage/Aktorik/Linearantriebe/Allgemein/Einbaulage @ 10\mod_1182147471406_3101.doc @ 107216
All mounting orientations shown in and fig. Fig. 4 are permissible. To facilitate mounting and
maintenance, however, it is recommended to use orientation IMV 1. For each mounting
position, check the oil level prior to commissioning.
In order to ensure sufficient ventilation and space for motor de-/installation allow for min.
80 mm (3.15 inch).
Pos: 8.12 /Überschriften/1.1/1-spaltig/M - O/Montagehinweise @ 10\mod_1181632708234_3101.doc @ 103461
3.3
Installation instructions
Pos: 8.13 /Montage/Aktorik/Linearantriebe/RSD10...200/Montagehinweise @ 18\mod_1205131105921_3101.doc @ 168683
• Make sure that the actuator is accessible from all sides to ensure convenient hand wheel
operation, electrical connection, and replacement of assemblies.
• Avoid direct exposure to rain, snow and other environmental influences.
• In IMV 1 mounting position, the actuators are resistant against vibrational loading acc. to EN
60068-2-6, table C.2 up to 150 Hz and additionally 1 g / 30 min. If the operating conditions
do not clearly allow you to estimate whether the vibrational loading remains significantly
below the proven contingent, reduce the maintenance intervals accordingly.
• Make sure that the thrust rod and the valve stem are not exposed to additional vibrational
loading that exceeds by double the rated force (e.g., by a spring coupling or a vibration
absorber between thrust rod and valve stem).
• The maximum rated force of the actuator may not be permanently exceeded. For a short
period, the force can be increased by up to twice the rated force is permitted.
• When mounting the actuator close to heat sources use an insulating layer or shielding.