68
| RMC-100| 2105552MNAE
Figure 4-27: PCCU32 Expert view
4.9.2
Analog input configuration
To configure the analog input:
1.
Click
I/O System
on the navigation tree. The Analog Inputs tab displays (
Figure 4-28: Analog input configuration
2.
Click the
Signal
field and select 0-30 Volt or 4-20 mA from the drop-down list.
3.
Click
Send
.
4.9.3
Analog output configuration
This configuration defines the AO value as a percentage of the full scale, or in engineering units. The
engineering units depend on the type of external device that connects to the AO.
Calibrate the AO before defining non-default engineering units for the first time. Define engineering
units from the AO Calibration screen after calibration is complete. These defined engineering units
automatically display on the Analog Output tab (
Figure 4-29: Analog output configuration
4.9.4
Digital input and output configuration
The six (6) DI/DO ports support configurable input or output modes of operation.
Configure input thresholds in input mode for an input voltage range of 0 to 30 Vdc. Configure the
built-in pull-up resistor to read signals from devices with dry contact and open collector/drain output
types.
In output mode, a MOSFET Open Drain (OD) type output can sink up to 2 amps (direct current).
To configure each digital input or output:
1.
Click
I/O System
on the navigation tree.
2.
Click the
Digital I/Os
tab (