Table 8. Signal outputs (Digital output module DOM)
Description
Value
Rated voltage
250V AC/DC
Continuous contact carry
5A
Make and carry for 3.0 s
10A
Make and carry for 0.5 s
15A
Breaking capacity when the control-circuit time constant L/
R < 40 ms, at 48/110/220V DC
1A / 0.25A / 0.15A
Table 9. Communication interface (Communication module LECM)
Cable
Data transfer
Shielded twisted pait cable, at minimum CAT5e with
RJ-45 connector
10/100 MBits/s
Table 10. Degree of protection by enclosure
Description
value
Degree of protection
IP20
Table 11. Environmental conditions
Description
Value
Operating temperature range
-40...+70ºC
Relative humidity
< 93%
Atmospheric pressure
86...106 kPa
Altitude
up to 2000 m
Transport and storage temperature range
-40...+85ºC
Table 12. Environmental tests
Description
Type test value
Reference
Dry heat test
• 96 h at +70ºC
IEC 60068-2-2
Dry cold test
• 96 h at -40ºC
IEC 60068-2-1
Damp heat test, cyclic
• 6 cycles at +25...55ºC, humidity >
93%
IEC 60068-2-30
Storage test
• 96 h at +85ºC
• 96 h at -40ºC
IEC 60068-2-48