Installation
42/68-167-EN
RHDE250 ... 4000 (Contrac)
13
Pos: 11.1 /Überschriften/1/M - R/Montage @ 0\mod_1140519732218_3101.doc @ 3159
4 Installation
Pos: 11.2 /Überschriften/1.1/1-spaltig/A - F/Antriebskontrolle @ 10\mod_1181632527031_3101.doc @ 103415
4.1
Actuator check
Pos: 11.3 /Montage/Aktorik/Elektr. Schwenkantriebe/Allgemein/Antriebskontrolle @ 10\mod_1181568760671_3101.doc @ 103037
Before you start to install the actuator make sure that the delivery status corresponds to the
ordered status and to the intended use.
• Check the oil level when installing the device in positions other than IMB 3.
• Did you fasten the separately delivered venting plug (spare part no. 9287338) in the
uppermost bore (depending on the mounting orientation)?
• Make sure that the motor and the connection chambers are free of dirt, moisture and
corrosion.
Pos: 11.4 /Überschriften/1.1/1-spaltig/A - F/Einbaulage @ 3\mod_1158651041937_3101.doc @ 41702
4.2
Mounting position
Pos: 11.5 /Montage/Aktorik/Elektr. Schwenkantriebe/RHDE250...4000/Einbaulage Zeichnung @ 10\mod_1181815089156_3101.doc @ 106121
The spur gears of the actuator RHDE250 ... 4000 (Contrac) are oil lubricated. They contain the
max. oil quantity when leaving the manufacturer. Once the actuator is installed replace the
uppermost check plug by the separately supplied venting plug.
IMB 3
IMB 6
IMB 7
IMV 6
1
2
M00304
Fig. 3
1
Inspection plug
2
Venting plug
Pos: 11.6 /Montage/Aktorik/Elektr. Schwenkantriebe/RHDE250...4000/Einbaulage RHDE250...4000 @ 10\mod_1181633075968_3101.doc @ 103484
All mounting orientations shown in fig. Fig. 3 are permissible. To facilitate mounting and
maintenance, however, it is recommended to use orientation IMB 3. For each mounting
position, check the oil level prior to commissioning.
In order to ensure sufficient ventilation and space for the motor de-/installation allow for the
following min. space to the motor hood:
Actuator
Space
RHDE250
60 mm (2.36 inch)
RHDE500/800
60 mm (2.36 inch)
RHDE1250/2500
80 mm (3.15 inch)
RHDE4000
80 mm (3.15 inch)
Pos: 11.7 /======= Seitenumbruch ======== @ 0\mod_1126532365768_3101.doc @ 3830
Содержание RHDE1250
Страница 47: ......