2.3.6.3
LD0.TRPPTRC2 Global conditioning (2)
Table 22:
LD0.TRPPTRC2 Global conditioning (2)
IEC 61850 name
SA name
Description
Values
.Op.general
-
Operate input signal
1=Operate
.Tr.general
-
Trip output signal
1=Trip
2.3.6.4
LD0.FRPFRQ1 Frequency protection (1)
Table 23:
LD0.FRPFRQ1 Frequency protection (1)
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC1
.Str.general
START
Stage start
1=Start
LD0.FRPTOF1
Overfrequency
.Op.general
OPR_OFRQ
-Operate
1=Operate
LD0.FRPTUF1
Underfrequency
.Op.general
OPR_UFRQ
-Operate
1=Operate
LD0.FRPFRC1
Frequency gradient
.Op.general
OPR_FRG
-Operate
1=Operate
2.3.6.5
LD0.FRPFRQ2 Frequency protection (2)
Table 24:
LD0.FRPFRQ2 Frequency protection (2)
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC2
.Str.general
START
Stage start
1=Start
LD0.FRPTOF2
Overfrequency
.Op.general
OPR_OFRQ
-Operate
1=Operate
LD0.FRPTUF2
Underfrequency
.Op.general
OPR_UFRQ
-Operate
1=Operate
LD0.FRPFRC2
Frequency gradient
.Op.general
OPR_FRG
-Operate
1=Operate
2.3.6.6
LD0.FRPFRQ3 Frequency protection (3)
Table 25:
LD0.FRPFRQ3 Frequency protection (3)
IEC 61850 name
SA name
Description
Values
LD0.FRPTRC3
.Str.general
START
Stage start
1=Start
LD0.FRPTOF3
Overfrequency
Table continues on next page
1MRS757056 C
Section 2
DNP3 data mappings
REU615
21
Point List Manual