5. Press
to confirm the selection. The selected language is shown on the display.
6. Press
to return the display to the idle mode.
By pressing
before confirming the selection, the former language remains active
and the display is returned to the view mode. Pressing
again returns the display
to the idle mode.
TRIP CIRCUIT SUP
Main Menu
Group Menu
Parameter Menu
Confirm
Cancel
SETTINGS
CONFIGURATION
MEASUREMENTS
RECORDED DATA
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
FREQUENCY
CONFIGURATION
CONFIGURATION
MEMORY SETTINGS
HMI PASSWORDS
TIME
INFO
ENGLISH
SVENSKA
SUOMI
U NOMINAL
OPERATION
STORE COUNTER
A050369_2
Fig. 4.1.8.-1
Selecting language
The list of languages in the language selection menu differs depending
on the HMI language set number in the order number.
4.1.9.
How to set the real-time clock
The real-time clock used for time-stamped events is set via two different settings,
one for Year-Month-Day and another for Hours-Minutes-Seconds.
To change one setting or both settings:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select
CONFIGURATION\TIME
and press
.
3. Use
or
to select the parameter to be edited.
4. Press
to enter the setting mode and give the password, if required. If the
default password 999 is still valid, no password is required.
22
REU 610
REU 610
Voltage Protection Relay
Operator's Manual
1MRS755770