Section 6
Differential protection
6.1
Transformer differential protection
6.1.1
Functionality
The Transformer differential protection, two-winding T2WPDIF and Transformer
differential protection, three-winding T3WPDIF are provided with internal CT ratio
matching and vector group compensation and settable zero sequence current
elimination.
The function can be provided with two or three three-phase sets of current inputs. All
current inputs are provided with percentage bias restraint features, making the IED
suitable for two- or three-winding transformer arrangements.
Two-winding applications
xx05000048.vsd
IEC05000048 V1 EN
two-winding power
transformer
Three-winding applications
xx05000052.vsd
IEC05000052 V1 EN
three-winding power
transformer with all
three windings
connected
xx05000049.vsd
IEC05000049 V1 EN
three-winding power
transformer with
unconnected delta
tertiary winding
Figure 29:
CT group arrangement
for differential
protection and other
protections
The setting facilities cover the application of the differential protection to all types of
power transformers and auto-transformers with or without load tap changer as well as
shunt reactors and local feeders within the station. An adaptive stabilizing feature is
included for heavy through-faults.
1MRK 504 135-UEN A
Section 6
Differential protection
79
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...