The SMAI function is used within PCM600 in direct relation with the Signal Matrix
tool or the Application Configuration tool.
The SMAI function blocks for the 650 series of products are possible
to set for two cycle times either 5 or 20ms. The function blocks
connected to a SMAI function block shall always have the same cycle
time as the SMAI block.
17.9.2
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Signal matrix for analog inputs
SMAI_20_x
-
-
17.9.3
Function block
SMAI_20_1
BLOCK
DFTSPFC
REVROT
^GRP1L1
^GRP1L2
^GRP1L3
^GRP1N
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
IEC09000137-1-en.vsd
IEC09000137 V1 EN
Figure 258:
SMAI_20_1 function block
SMAI_20_2
BLOCK
REVROT
^GRP2L1
^GRP2L2
^GRP2L3
^GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
IEC09000138-2-en.vsd
IEC09000138 V2 EN
Figure 259:
SMAI_20_2 to SMAI_20_12 function block
Note that input and output signals on SMAI_20_2 to SMAI_20_12 are
the same except for input signals GRPxL1 to GRPxN where x is equal
to instance number (2 to 12).
1MRK 504 135-UEN A
Section 17
Basic IED functions
581
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...