actually set and configured values within the IED. No settings will be changed, thus
mistakes are avoided.
Forcing of binary output signals is only possible when the IED is in test mode.
17.4.3
Function block
TESTMODE
INPUT
ACTIVE
OUTPUT
SETTING
NOEVENT
IEC09000219-1.vsd
IEC09000219 V1 EN
Figure 256:
TESTMODE function block
17.4.4
Signals
Table 487:
TESTMODE Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Sets terminal in test mode when active
Table 488:
TESTMODE Output signals
Name
Type
Description
ACTIVE
BOOLEAN
Terminal in test mode when active
OUTPUT
BOOLEAN
Test input is active
SETTING
BOOLEAN
Test mode setting is (On) or not (Off)
NOEVENT
BOOLEAN
Event disabled during testmode
17.4.5
Settings
Table 489:
TESTMODE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
TestMode
Off
On
-
-
Off
Test mode in operation (On) or not (Off)
EventDisable
Off
On
-
-
Off
Event disable during testmode
CmdTestBit
Off
On
-
-
Off
Command bit for test required or not
during testmode
1MRK 504 135-UEN A
Section 17
Basic IED functions
575
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...