9.4.7.6
Logic diagram
IEC09000161_3_en.vsd
t
t
t
1
&
&
Ei
M=
(Ei / f)
(Ur / fr)
M = relative V/Hz as service value
V/Hz>>
M>V/Hz>>
V/Hz>
M>V/Hz>
tAlarm
tMin
kForIEEE
Calc ulation
of inte rnal
induced
voltage Ei
k
M
M
t>tAlarm
t>tMin
ALARM
AlarmL evel
1800 s
U3P
BLOCK
100 ms
TRIP
IEC09000161 V3 EN
Figure 101:
A simplified logic diagram of the Overexcitation protection
OEXPVPH
Simplification of the diagram is in the way the IEEE delays are calculated. The
cooling process is not shown. It is not shown that voltage and frequency are separately
checked against their respective limit values.
9.4.8
Technical data
Table 153:
OEXPVPH technical data
Function
Range or value
Accuracy
Operate value, start
(100–180)% of (
UBase/f
rated
)
± 0.5% of U
Operate value, alarm
(50–120)% of start level
± 0.5% of U
r
at U ≤ U
r
± 0.5% of U at U > U
r
Operate value, high level
(100–200)% of (
UBase/f
rated
)
± 0.5% of U
Curve type
IEEE
2
(0.18 )
:
(
1)
k
IEEE t
M
×
=
-
EQUATION1319 V1 EN
(Equation 85)
where M = (E/f)/(Ur/fr)
± 5% + 40 ms
Minimum time delay for inverse
function
(0.000–60.000) s
± 0.5% ± 25 ms
Alarm time delay
(0.00–9000.00)
± 0.5% ± 25 ms
Section 9
1MRK 504 135-UEN A
Voltage protection
230
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...