E
f
fr
V Hz >
£
IECEQUATION2297 V2 EN
(Equation 79)
where:
V/Hz> is the maximum continuously allowed voltage at no load, and rated frequency.
V/Hz>
is a setting parameter. The setting range is 100% to 180%. If the user does not
know exactly what to set, then the default value for
V/Hz>
= 110 % given by the IEC
60076-1 standard shall be used.
In OEXPVPH, the relative excitation M is expressed according to equation
.
( )
E f
M p.u. =
Ur fr
IECEQUATION2299 V1 EN
(Equation 80)
It is clear from the above formula that, for an unloaded power transformer, M = 1 for
any E and f, where the ratio E/f is equal to Ur/fr. A power transformer is not
overexcited as long as the relative excitation is M ≤
V/Hz>
,
V/Hz>
expressed in % of
Ur/fr.
It is assumed that overexcitation is a symmetrical phenomenon, caused by events such
as loss-of-load, etc. A high phase-to-earth voltage does not mean overexcitation. For
example, in an unearthed power system, a single phase-to-earth fault means high
voltages of the “healthy” two phases-to-earth, but no overexcitation on any winding.
The phase-to-phase voltages will remain essentially unchanged. The important
voltage is the voltage between the two ends of each winding.
9.4.7.1
Measured voltage
A check is made if the Selected voltage signal is higher than 70% of the rated phase-to-
earth voltage. When below this value, OEXPVPH exits immediately and no excitation
is calculated.
The frequency value is received from the pre-processing block. The function operates
for frequencies within the range of 33-60 Hz and of 42-75 Hz for 50 Hz and 60 Hz
respectively.
•
OEXPVPH can be connected to any power transformer side, independent from
the power flow.
•
The side with a load tap changer must not be used, since the tap changer can
change the relative excitation (M)
1MRK 504 135-UEN A
Section 9
Voltage protection
225
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...