Name
Values (Range)
Unit
Step
Default
Description
U1>
1 - 200
%UB
1
30
Voltage start value (DT & IDMT) in % of
UBase for step 1
t1
0.00 - 6000.00
s
0.01
5.00
Definite time delay of step 1
t1Min
0.000 - 60.000
s
0.001
5.000
Minimum operate time for inverse curves
for step 1
k1
0.05 - 1.10
-
0.01
0.05
Time multiplier for the inverse time delay
for step 1
OperationStep2
Off
On
-
-
On
Enable execution of step 2
U2>
1 - 100
%UB
1
45
Voltage start value (DT & IDMT) in % of
UBase for step 2
t2
0.000 - 60.000
s
0.001
5.000
Definite time delay of step 2
Table 145:
ROV2PTOV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
9.3.6
Monitored data
Table 146:
ROV2PTOV Monitored data
Name
Type
Values (Range)
Unit
Description
ULevel
REAL
-
kV
Magnitude of measured
voltage
9.3.7
Operation principle
Two step residual overvoltage protection ROV2PTOV is used to detect earth (zero
sequence) overvoltages. The ground overvoltage 3U
0
is normally computed by
adding the input phase voltages. 3U
0
may also be input single phase by either
measuring directly from a voltage transformer in the neutral of a power transformer,
or from a secondary broken delta connection of a transformer with a star-grounded
primary. ROV2PTOV has two steps with separate time delays. If the ground
overvoltage remains above the set value for a time period corresponding to the chosen
time delay, the corresponding TRIP signal is issued.
The time delay characteristic is setable for step 1 and can be either definite or inverse
time delayed. Step 2 is always definite time delayed.
The voltage related settings are made in percent of the global phase-to-phase base
voltage divided by √3.
Section 9
1MRK 504 135-UEN A
Voltage protection
218
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...