R
jx
Mho, zone3
Mho, zone2
Mho, zone1
IEC09000172_1_en.vsd
IEC09000172 V1 EN
Figure 56:
Mho, offset mho characteristic
Zone 3 can be equipped with a load encroachment function which cuts off a section of
the characteristic when enabled. The function is activated by setting the parameter
LoadEnchModZ3
to
On
. Enabling of the load encroachment function increases the
possibility to detect high resistive faults without interfering with the load impedance.
The algorithm for the load encroachment is located in the Load encroachment
(LEPDIS) function, where the relevant settings can be found. Information about load
encroachment from LEPDIS function to zone measurement is sent via the input signal
LDCND in binary format.
7.2.6.3
Basic operation characteristics
Each impedance zone can be enabled and disabled by setting
OpModeZx
(where
x
is
1-3 depending on selected zone).
The zone reach for phase-to-phase fault is set individually in polar coordinates. The
impedance is set by the parameter
ZxFwd
and
ZxRev
and the corresponding arguments
by the parameter
ImpedanceAng
. The setting
ImpedanceAng
is common for all three
zones.
Section 7
1MRK 504 135-UEN A
Impedance protection
134
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...